Plan Review Notes
Plan Review Notes For Permit 07070693
Permit Number 07070693
Review Stop B
Sequence Number 1
Notes
Date Text
2007-08-10 18:56:41BUILDING PLAN REVIEW
 PERMIT:07070693
 ADD: 600 S.ROSEMARY AVE
 CONT: SCHERER CONST.
 TEL: (407)894-7661
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2)110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PROJECT IS DESIGNED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED
 F) WHETHER THE SPRINKLER SYSTEM IS REQUIRED.
 G) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT
 . -------------------------------------
 ) NUMBER OF FLOORS
 ) NUMBER OF ROOMS
 ) SQ. FT. FOOTPRINT
  
 3)2004 FBC EXISTING
 301.5A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
  
 4)A TITLE BLOCK WITH THE INFORMATION SPECIFIED PER
 61G1-16.004 FAC SHALL BE PRESENT ON DRAWINGS ISSUED BY
 THE RESPONSIBLE ARCHITECT AND MUST, AT A MINIMUM
 CONTAIN
 1) FIRM NAME,ADDRESS, AND TELEPHONE #
 2) FIRM LICENCE #
 3) NAME OF PROJECT
 4) DATE PREPARED
 5) A SPACE FOR SIGNATURE & DATED SEAL
 6) A SPACE FOR PRINTED NAME OF PERSON
 SEALING THE DOCUMENT.
 THE COMPLETE ADDRESS INCLUDING THE SUITE NUMBER SHALL
 BE INCLUDED ON EACH SHEET.
  
 5)SHEET A-1. DEMOLITION NOTE #8 INDICATES THE
 PREVIOUS USE OF THE SPACE WAS MERCANTILE AND IS NOW
 BEING CHANGE TO BUSINESS. INDICATE ON THE DRAWINGS THE
 PREVIOUS OCCUPANCY AND THE PROPOSED OCCUPANCY. ON THE
 APPLICATION CHECKYES OR NO FOR CHANGE OF OCCUPANCY
 USE.
  
 6)INTERIOR FINISHES SHALL MEET THE REQUIREMENTS OF
 FBC. SECTIONS 803/804 AND 805. INDICATE CLEARLY ON THE
 DRAWINGS HOW THESE REQUIREMENTS ARE MET.
  
 7)FBC.1210.1THE FLOORS OF TOILET ROOMS ACCESSIBLE
 TO THE PUBLICSHALL HAVE A SMOOTH,HARD, NONABSORBENT
 SURFACE AND SHALL EXTEND AT LEAST 6 INCHES UPWARD.
 WALLS WITHIN 2 FEET OF UNIRALS AND WATER CLOSETS SHALL
 ALSO HAVE A SMOOTH "HARD" NONABSORBENT SURFACE TO A
 HEIGHT OF 4 FEET ABOVE THE FLOOR. FBC. 1210.2. SHOW
 THIS INFORMATION ON THE DRAWINGS. PAINT ON DRYWALL IS
 NOT CONSIDER AS A "HARD" SURFACE.
  
 8)FBC 11-7.2(2)(I)A PORTION OF THE MAIN COUNTER
 SHALL BE 36 INCHES MINIMUM LENGTHAND 36 INCHES
 MAXIMUM HEIGHT. PROVIDE ELEVATION DETAIL DRAWINGS
 SHOWING COMPLIANCE WITH THIS SECTION.
  
 NOTE: SEE 2004FLORIDA EXISTING BUILDING CODE CH.8 FOR
 FURTHER INFORMATION.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved