| Notes |
| Date |
Text |
| 2007-09-25 11:41:05 | *****DENIED***** | | | | | | THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS REVIEW | | | STILL NEED TO BE ADDRESSED: | | | | | | | | | 3.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE | | | REFERENCED.REFERENCE THE 2003 EDITION, NOT THE 2000 | | | EDITION AS INDICATED ONA-1.2 | | | | | | 4.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | REFERENCE 241, NOT 242 AS INDICATED ON A-1.2 | | | | | | 7.PROVIDE A LIFE SAFETY PLAN WHICH SHOWS TRAVEL | | | DISTANCE TO THE EXIT, LOCATION OF FIRE EXTINGUISHER(S), | | | EXIT AND EMERGENCY LIGHTS.TRAVEL DISTANCE NOT SHOWN; | | | THE TRAVEL DISTANCE TO AN EXIT SHALL BE MEASURED AS PER | | | 7.6.1 OF NFPA 101 | | | | | | 8.SPECIFY THE INTERIOR FINISH MATERIAL MATERIALS FOR | | | THE NEW WALLS IN TERMS OF CLASS A, CLASS B, OR CLASS C. | | | INDICATE CLASSIFICATIONS FOR EXITS, EXIT AISLE | | | CORRIDORS, AND OTHER SPACES ON A-2.2 | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|