Plan Review Notes
Plan Review Notes For Permit 07070672
Permit Number 07070672
Review Stop P
Sequence Number 1
Notes
Date Text
2007-09-07 07:47:58DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. THE DESIGNER IS NOT APPROVED TO DESIGN COMMERCIAL
 PLANS. SEE FS 481.003 AND FS R71.003.
  
 2. SHT C-1 "ADDITION TO EXISTING STRUCTURE NOTES"
 BRINGS UP TWO QUESTIONS. (1) IS THIS AN ADDITION TO THE
 EXISTING BUILDING? & (2) FINAL NOTES INDICATES A SECOND
 ENGINEER OF RECORD. PLEASE CLARIFY. SECTION 106.1.1.
 (SEE APPLICATION "DESCRIBE PROJECT IN DETAIL" (FAILURE
 TO DO SO MAY RESULT IN DELAYS).
  
 3. SHT A-1 DETAIL A DOES NOT REFLECT THE ACTUAL
 ACCESSIBLE TOILET ROOM. SHOW THE CLEAR FLOOR SPACE &
 TURNING AREA REQUIREMENTS IN THE TOILET ROOM INDICATED
 ON THE FLOOR PLAN, OR CHANGE THE DETAIL TO REFLECT THE
 FLOOR PLAN AND SHOW THE REQUIREMENTS IN THE DETAIL.
 SHOW THE FOLLOWING:
 ___FOR W/C
 A. 11-4.16.2 CLEAR FLOOR SPACE
 ___FOR LAV
 A. 11-4.19.3 CLEAR FLOOR SPACE
 ___FOR TOILET ROOM
 A. 11-4.22.2(1) DOOR SHALL NOT SWING INTO THE CLEAR
 FLOOR SPACE REQUIRED FOR ANY FIXTURE
  
 4. PER TABLE 403.1 A DRINKING FOUNTAIN AND A SERVICE
 SINK ARE REQUIRED. PLEASE INDICATE THE LOCATION OF BOTH
 REQUIRED FIXTURES.
  
 5. PER SECTION 607.1 HOT WATER WILL BE REQUIRED TO THE
 SERVICE SINK.
  
 6. SUBMIT A DETAIL FOR THE DRINKING FOUNTAIN SHOWING
 COMPLIANCE WITH SECTION 11-4.15 AND ALL SUBSECTIONS AS
 WELL AS SECTION 11-4.1.3(10)(A) PROVISIONS FOR THOSE
 WHO HAVE DIFFICULTY BENDING OR STOOPING.
  
 7. SHT E-1 THE PLUMBING RISER DIAGRAM DOES NOT REFLECT
 THE FLOOR PLAN. AS SHOWN THE LAV & W/C ARE IN THE SAME
 LOCATION. (SEE RED LINE EXAMPLE OF HOW TO SHOW THE LAV
 NEXT TO THE W/C). SECTION 106.1.1.
  
 8. SUBMIT A WATER RISER DIAGRAM. SHOW ALL PIPE SIZES,
 VALVES, RPZV BACKFLOW & (IF REQD. BY SECTION 604.9
 WATER HAMMER ARRESTORS). SECTIONS
 106.3.5.1.3(3)(8)(10)(13), 604,606 & 608.13.2.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved