Plan Review Notes
Plan Review Notes For Permit 07070672
Permit Number 07070672
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-09-17 13:38:14*****DENIED*****
  
  
 1.THE 2003 EDITION OF NFPA 101 (LIFE SAFETY CODE)
 SHALL BE REFERENCED.
  
 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 3.SHOW ON THE PLANS THE SCOPE OF WORK THAT IS TO BE
 CONDUCTED.
  
 4.NO EXIT LIGHTS AND EMERGENCY LIGHTING SHOWN IN THE
 EXISTING WAREHOUSE.
  
 5. HOW/WHERE IS ENTRY MADE INTO THE EXISTING OFFICE.
  
 6.PROVIDE A TRAVEL DISTANCES TO THE EXITS.PROVIDE
 THE THE LOCATION OF 2A:10 BC RATED FIRE EXTINGUISHER(S)
 WHICH SATISFIES THE 75' TRAVEL DISTANCE.
  
 7.PROVIDE A LAYOUT OF THE FIRE SPRINKLER SYSTEM.ANY
 REMODEL TO THIS SYSTEM SHALL REQUIRE SEPARATE PLANS AND
 PERMIT.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE PLAN EACH ITEM WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-8-05-6722