| Notes |
| Date |
Text |
| 2007-09-17 13:38:14 | *****DENIED***** | | | | | | | | | 1.THE 2003 EDITION OF NFPA 101 (LIFE SAFETY CODE) | | | SHALL BE REFERENCED. | | | | | | 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | | | 3.SHOW ON THE PLANS THE SCOPE OF WORK THAT IS TO BE | | | CONDUCTED. | | | | | | 4.NO EXIT LIGHTS AND EMERGENCY LIGHTING SHOWN IN THE | | | EXISTING WAREHOUSE. | | | | | | 5. HOW/WHERE IS ENTRY MADE INTO THE EXISTING OFFICE. | | | | | | 6.PROVIDE A TRAVEL DISTANCES TO THE EXITS.PROVIDE | | | THE THE LOCATION OF 2A:10 BC RATED FIRE EXTINGUISHER(S) | | | WHICH SATISFIES THE 75' TRAVEL DISTANCE. | | | | | | 7.PROVIDE A LAYOUT OF THE FIRE SPRINKLER SYSTEM.ANY | | | REMODEL TO THIS SYSTEM SHALL REQUIRE SEPARATE PLANS AND | | | PERMIT. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING WHERE ON THE PLAN EACH ITEM WAS | | | ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-8-05-6722 |
|