Plan Review Notes
Plan Review Notes For Permit 07070672
Permit Number 07070672
Review Stop E
Sequence Number 1
Notes
Date Text
2007-08-13 18:15:16** DENIED **
  
  
  
 1) NOTE: PLEASE SEE THE PLANS AS SUBMITTED MAY NOT BE
 DONE BY THE DESIGNER AS STATED ON THE TITLE BLOCKS.
 THE PLANS WHICH ARE SIGNED AND SEALED BY AN ENGINEER
 ARE ALSO INDICATING BEING DONE BY A *DESIGNER* WHO IS
 NOT LICENSED UNDER FLORIDA STATUTES TO PERFORM THIS
 SCOPE OF WORK. PLEASE SEE FS 481.229, 471.003 ETC.
 PLEASE ALSO SEE BUILDING REVIEW COMMENTS AS CASE LAW
 WILL FROM THE STATE WILL BE PROVIDED.
 PLEASE SEE THIS SCOPE OF WORK MAY ONLY BE DONE UNDER
 LICENSURE AS ACCEPTED PER 481/471 AND POSSIBLY 489 OF
 THE FLORIDA STATUTES.
 PLANS MAY BE RETAINED BY THIS OFFICE.
  
 2) NOTE: PLEASE SEE THE FOLLOWING MINIMUM CODES ARE
 REQUIRED TO BE STATED ON PLANS.
 2004 FBC W/2006 REVISIONS.
 2005 NFPA-70 (DONE).
 2003 NFPA-101
 2002 NFPA-72
 SEE COMMENTS FROM OTHER TRADES WHICH MAY REQUIRE MORE
 INFORMATION AND/OR RELEVANT CODES.
  
 3) NOTE: PLEASE SEE THAT NOT ENOUGH INFORMATION IS
 BEING PROVIDED FOR ELECTRICAL WORK TO BE DONE.
 PLEASE SEE BUILDING REVIEW COMMENTS FOR LEVEL OF
 ALTERATION REQUIRED TO BE STATED ON PLANS.
 PLEASE SEE NO CIRCUITING IS SHOWN ON PLANS. FBC
 106.3.5.1.2, 106.1.2, NEC 408.4
 PLEASE SEE NO PANEL SCHEDULE SHOWING BRANCH CIRCUIT
 SIZES, OVER CURRENT PROTECTION, CONDUCTORS, BREAKERS.
 408.4, 310.16, 240.4 ETC
 PLEASE SEE NO LOAD CALCULATIONS FOR INCREASED LOADS AND
 EXISTING LOADS WERE SUBMITTED. NEC 220, 408 ETC
 PLEASE SEE NO INFORMATION FOR EMERGENCY LIGHTING/EXIT
 LIGHTING PER LS 101 7.8, 7.9 AND NEC 700.12F
 PLEASE SEE NO INFORMATION FOR FBC CHAPTER 13, 13-101,
 13-415.1.ABC.1.1 FOR LIGHTING CONTROLS,13-415.2 FOR
 PERFORMANCE CALCULATIONS.
  
 ** PLEASE SUBMIT PLANS FOR MINIMUM CODE COMPLIANCE FOR
 SCOPE OF WORK TO BE PERFORMED CLEARLY SHOWN AND STATED
 ON PLANS AND DESIGNS PER FBC, NEC AND ALL CODES AS
 NOTED ABOVE IN NOTE #1.
  
 ** PLEASE KNOW AS THERE ARE SEVERAL ITEMS ARE NOT YET
 SUBMITTED FOR FULL REVIEW.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  