2007-08-16 20:09:50BUILDING PLAN REVIEW
 PERMIT: 07070672
 ADD: 917 N RAILROAD AVE
 CONT: ANNUNZIATA BUILDING
 TEL: (561)906-9300
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) DESIGNER: JULIE MONDELL DESIGNS,IS ADVERTISING
 WITH NAME IN THE TITLE STRIP. ACTING AS A DESIGN
 PROFESSIONAL, IF LICENSED AS A DRAFTSMAN THEY CAN ONLY
 DO RESIDENTIALNOT BUSINESS. PLEASE SEE FLORIDA STATE
 STATUTES 471.003 ENGINEERING AND 481.003 FOR
 ARCHITECTURE AS TO WHO CAN DESIGN AND EXEMPTIONS.
  
 4) SHEET C-1 COVERSHEET:
 4A) CODE AND LIFE SAFETY INFORMATION, PLEASE CORRECT
 THE CODE EDITION TO REFLECT THE 2004 FBC BUILDING WITH
 2006 AMENDMENTS.
 4B) PLEASE REVISIT SHELL CONSTRUCTION TYPE FOR UNDER
 THE 2004 FBC THIS IS HEAVY TIMBER. SEE TABLE 503. 4C)
 ADDITION TO EXISTING STRUCTURE NOTES, WHERE IS THE
 ADDITION AND WHY IS A 2ND ENGINEER ASSIGNED TO THIS
 PROJECT, SEE NOT #4 BUNKER ENGINEERING P E?
 4D) THE PERMIT APPLICATION NOR THE PLAN ACTUALLY
 INDICATES WHAT WORK IS TO BE COMPLETED UNDER THIS
 PERMIT? ADDITIONAL INFORMATION IS REQUIRED 106.1.2? 4E)
 PLEASE PROVIDE WHAT TYPE OF MATERIALS ARE GOING TO BE
 STORED IN THIS BUILDING AND QUANITIES?ADDITIONAL
 INFORMATION IS REQUIRED 106.1.2?
  
 5) SHEET A-1:
 5A)PLEASE PROVIDE INFORMATION AS TO WHERE THE DOOR IS
 TO THE OFICE?
 5B) IS THERE A MEZZANINE OR SECOND FLOOR/
 5C) PLEASE CORRECT THE DETAIL A TO COENCIDE WITH THE
 ACTUAL RESTROOM IN THE SHEET A-1. PROVIDE A BACKING
 DETAIL.
 5D) IN THE RESTROOM DEPICTED IN THE PLAN THE INSWING
 DOOR SWINGS INTO THE CLEAR FLOOR SPACE REQUIRED FOR THE
 WATER CLOSET.
 11-4.22.2 DOORS. ALL DOORS TO ACCESSIBLE TOILET ROOMS
 SHALL COMPLY WITH 11-4.13. DOORS SHALL NOT SWING INTO
 CLEAR FLOOR SPACE REQUIRED FOR ANY FIXTURE.
 5E) THERE IS A 1-HR RATED WALL DETAIL FOR SECTION B-B
 AS WELL AS A 2HR WALL DETAIL. WHAT IS THE 2HR RATED
 WALL DETAIL FOR? IS THIS A CHANGE OF OCCUPANCY FOR THIS
 UNIT?
 IS THE 2 HR RATED WALL DETAIL FOR A TENANT OR OCCUPANCY
 SEPERATION? 106.1.2* ADDITIONAL INFORMATION REQUIRED.
 5F)PLEASE PROVIDE A LIFE SAFETY PLAN INDICATING EXIT
 LIGHTS. 1006.1.4
 REQUIRED ILLUMINATION SHALL BE ARRANGED SO THAT THE
 FAILURE OF ANY SINGLE LIGHTING UNIT WILL NOT RESULT IN
 AN ILLUMINATION LEVEL IN ANY DESIGNATED AREA OF LESS
 THAN 0.2 FOOTCANDLE (2 LUX).
 5G) PLEASE PROVIDE AN OVERALL LAYOUT OF THE FIRE
 SPRINKLERS.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 BUILDING PLAN REVIEW II
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]