| 2007-08-07 16:58:19 | BUILDING REVIEW FOR STRUCTURAL REPAIRS. |
| | FIRST REVIEW CHECKLIST. |
| | REVIEW DONE UNDER FBC 2004BUILDING WITH 2006 |
| | REVISIONS AND 2004 FLORIDA RESIDENTIAL CODE: |
| | |
| | 1- PROVIDE PRODUCT APPROVAL AS REQUIRED BYDCA RULE |
| | 9B-72 FOR: |
| | A) NEW EXTERIOR WINDOWS AND DOORS. |
| | |
| | B) STORM SHUTTERS, UNLESS WINDOWS AND DOORS HAVE |
| | HURRICANE MISSILE IMPACT GLAZINGAS REQUIRED BY SEC. |
| | R301.2.1.2 OF 2004 FLORIDA RESIDENTIAL CODE. ***NOTE: |
| | PROVIDE COMPLETE INSTALLATION SCHEDULE. SEE ATTACHED |
| | SAMPLE.AND,CLEARLY CIRCLEON SHUTTERS DRAWINGS |
| | SPECIFIC MOUNTING CONDITIONS AND SPECIFIC ANCHOR TYPE |
| | AND SPACING TO BE USED. SEC. 106.1.2 CITY AMENDMENTS TO |
| | FBC 2004. |
| | |
| | C) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON |
| | PLANS AND DETAILS. |
| | |
| | 2- SPECIFY CONSTRUCTION TYPE AS REQUIRED BY SEC. 602.1 |
| | FBC 2004 AND SEC. 106.3.5.4 CITY AMENDMENTS TO FBC |
| | 2004. |
| | |
| | 3- TYPICAL WALL SECTION ON SHEET 1 OF 1: |
| | A)PROVIDE COMPLETE TYPICAL WALL SECTION SHOWING |
| | CONNECTORS ON TOP AND BOTTOM OF WOOD STUDS. SEC. |
| | 106.1.2 CITY AMENDMENTS TO FB 2004. SECTION SHOWNIS |
| | INCOMPLETE. |
| | |
| | B)NEED TO REVISE SIMPSON ST18 STRAP SPECIFIED ON |
| | TYPICAL WALL SECTION SECTION.THIS IS A WOOD TO WOOD |
| | CONNECTOR.NEED TO SPECIFY A WOOD TO MASONRY |
| | CONNECTOR.SEE CURRENT SIMPSON CATALOG AND REVISE AS |
| | REQUIRED.SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| | |
| | C) PROVIDE COMPLETE SPECIFICATIONS FOR NEW STUCCO |
| | FINISH. PROVIDE COMPLETE WALL SHEATHING SPECS AND |
| | FASTENING, AND STUCCO FINISH AS REQUIRED BY ASTM C926 |
| | AND ASTM C1063. |
| | |
| | D) HOW CAN YOU RECONSTRUCT 2X4 STUD?.SEC. 106.1.2 |
| | CITY AMENDMENTS TO FBC 2004. |
| | |
| | 4- PROVIDEENERGY CALCULATIONSAS REQUIRED BY SEC. |
| | 13-600.1.C.2 FBC 2004. |
| | |
| | 5- SPECIFY SIZE AND TYPE OF WINDOW TO BE REPLACED AT |
| | BEDROOM WINDOW TO VERIFY COMPLIANCE WITH EGRESS |
| | REQUIREMENTS.SEC. 405 FBC 2004 EXISTING BUILDING. |
| | |