| Plan Review Notes For Permit 07070662 |
| Permit Number |
07070662 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-08-20 13:48:57 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2004 | | | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL | | | | | | 1.COMPLETE THE ATTACHED INSTALLATION SCHEDULE OR | | | PROVIDE ALL INFORMATION TO SHOW CODE COMPLIANCE IN | | | ANOTHER FORMAT, FBC*106.THE SCHEDULE YOU PROVIDED | | | DOES NOT HAVE ALL REQUIRED INFORMATION (FOR INSTANCE, | | | LACKING ANCHOR TYPE, SUBSTRATE) AND HAS TWO DIFFERENT | | | ANCHOR SPACINGS.SEE OPENINGS 2 AND 3."WALL-OVER | | | MOUNTING 6" IS SPECIFIED, BUT YOU'VE HIGHLIGHTED FLOOR | | | MOUNTING 6.CONNECTION TYPE SHOULD CORRELATE WITH THE | | | ANCHOR SCHEDULE ON THE PRODUCT APPROVAL.CODE | | | COMPLIANCE CANNOT BE DETERMINED. |
|