| Plan Review Notes For Permit 07070661 |
| Permit Number |
07070661 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-08-20 13:50:07 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2004 | | | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL | | | | | | 1.COMPLETE THE ATTACHED INSTALLATION SCHEDULE OR | | | PROVIDE ALL INFORMATION TO SHOW CODE COMPLIANCE IN | | | ANOTHER FORMAT, FBC*106.INFORMATION HIGHLIGHTED ON | | | THE PRODUCT APPROVAL CONFLICTS WITH THE INSTALLATION | | | SCHEDULE.THE SHUTTER MOUNTING DETAIL SHOULD CORRELATE | | | WITH THE ANCHOR SCHEDULES.DETAIL 5 USES CONNECTION | | | TYPE D, SEE DRAWING 2 OF 7.HOWEVER, YOU HAVE | | | HIGHLIGHTED CONNECTION TYPES A AND C.PLEASE EITHER | | | REVISE YOUR FORM TO PROVIDE ALL INFORMATION REQUIRED, | | | OR COMPLETE THE SAMPLE INSTALLATION SCHEDULE. | | | | | | |
|