| 2007-08-13 15:17:58 | ****CORRECTIONS**** |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | FBC FLORIDA BUILDING CODE 2004 |
| | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL |
| | |
| | SHUTTER PERMIT APPLICATION, ONLY CHECKED ITEMS APPLY |
| | |
| | ____1.PROVIDE BUILDING HEIGHT ON THE PLAN.DESIGN |
| | PRESSURES FOR BUILDINGS OVER 60FEET ARE REQUIRED TO BE |
| | DESIGNED USING ASCE7, FBC1609.1.1 AND MUST BE DONE BY A |
| | DESIGN PROFESSIONAL. DOCUMENTS PREPARED BY AN ARCHITECT |
| | OR ENGINEER AND SUBMITTED FOR PUBLIC RECORD ARE TO BE |
| | SIGNED SEALED ORIGINALS FAC61G15, FAC61G1 16. |
| | |
| | ____2.PROVIDE A COPY OF THE CONDO ASSOCIATION |
| | APPROVAL. |
| | |
| | ____3.COMPLETE THE ATTACHED INSTALLATION SCHEDULE |
| | OR PROVIDE ALL INFORMATION TO SHOW CODE COMPLIANCE IN |
| | ANOTHER FORMAT, FBC*106. |
| | |
| | ____4.FLORIDA STATE OR LOCAL PRODUCT APPROVAL |
| | REQUIRED, FAC9B72, WWW.FLORIDABUILDING.ORG. |
| | |
| | ____5.SHOW THE EMERGENCY MEANS OF ESCAPE, FBC |
| | R310. |
| | |
| | ____6.PROVIDE A FLOOR PLAN SHOWING WHERE THE |
| | SHUTTERS WILL BE INSTALLED AND PANEL SIZES WHICH |
| | CORRELATES WITH THE INSTALLATION SCHEDULE, ITEM 3 |
| | ABOVE. |
| | |
| | _XX_8.REVISE EXPOSURE CATEGORY FBC1609.6.2.1(2), |
| | FBC R301.2.1.4.NOTE THAT THE DEFINITION FOR EXPOSURE |
| | C HAS CHANGED EFFECTIVE DECEMBER 8, 2006 FBC1609.4, FBC |
| | R301.2.1.4.DESIGN PRESSURES TOO LOW. |
| | |
| | |