| Plan Review Notes For Permit 07070651 |
| Permit Number |
07070651 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-08-31 09:52:25 | 2004 FBC W/2007 SUPPLEMENTS | | | INSTALL HURRICANE IMPACT SCREENS | | | 2ND REVIEW | | | | | | DENIED BY BUILDING | | | | | | 1) THE IMPACT SCREEN MULLIONS DO NOT HAVE STATE OR | | | MIAMI-DADE PRODUCT APPROVALS AS REQUIRED BY FAC RULE | | | 9B-72. THE MANUFACTURER IS REQUIRED TO APPLY FOR | | | LOCAL/SITE SPECIFICPRODUCT APPROVAL. SEE ATTACHMENT. | | | FBC 1609.1.4 REQUIRES IMPACT-RESISTANT PRODUCTS TO BE | | | TESTED. | | | | | | 2) THE ENGINEERING SUBMITTED IS NOT ACCEPTABLE. FBC | | | 1609.1.4 REQUIRES IMPACT RESISTANT COVERINGS TO MEET | | | THE REQUIREMENTS OF SSTD 12, ASTM E 1886 AND ASTM E | | | 1996, OR MIAMI-DADE TAS 201, 202, AND 203. OPENINGS | | | LOCATED WITHIN 30 FEET OF GRADE SHALL MEET THE | | | REQUIREMENTS OF THE LARGE MISSLE TEST. SUBMIT LARGE | | | MISSILE IMPACT TEST REPORTS SPECIFIED FOR THE | | | MULLIONS. | | | | | | 3)A RECORDED COPY OF THE NOTICE OF COMMENCEMENT | | | MUST BE SUBMITTED BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | - ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|