Plan Review Notes
Plan Review Notes For Permit 07070644
Permit Number 07070644
Review Stop E
Sequence Number 2
Notes
Date Text
2007-10-03 07:31:08 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 THE FOLLOWING COMMENTS WERE NOT CORRECTLY ADDRESSED IN
 THE PREVIOUS REVIEW. AN * AFTER THE COMMENTINDICATES
 FURTHER EXPLANATION.
  
 1} DUE TO THE METER LOCATION, A DISCONNECT IS REQUIRED
 PER 230.70, 225.32. INDICATE LOCATION ON PLAN PER
 230.70(A)(1)* THE DISCONNECT ON THE PLAN WAS NOT
 INCLUDED IN THE RISER DIAGRAM.SHOW EQUIPMENT GROUND
 WHERE REQUIRED (ON THE LOAD SIDE OF THE DISCONNECT) AND
 SIZE SAME PER 250.122.
  
 4} THE DINING ROOM RECEPTACLE CIRCUIT #27, MUST BE A 20
 AMP CIRCUIT PER 210.52(B)(1). * THE DESIGNER HAS LEFT A
 # 14 CONDUCTOR ON A 20 AMP CIRCUIT BREAKER IN VIOLATION
 OF 310.16, AND THE CIRCUIT RATED AT 543 (KVA?) WHEN PER
 220.52(A) IT MUST BE 1500 VA. NOTE: ALL RATINGS ARE
 INCORRECTLY NOTED AS KVA PER THE HEADING OF THAT
 COLUMN.
  
 6} THE DISCONNECTING MEANS LOCATED AT THE A/C EQUIPMENT
 (BOTH UNITS) DO NOT INDICATE COMPLIANCE WITH THE
 CLEARANCE REQUIREMENTS OF 110.26.* NOT ADDRESSED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718