| Plan Review Notes For Permit 07070644 |
| Permit Number |
07070644 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-10-03 07:31:08 | | | | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | | COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | | | THE FOLLOWING COMMENTS WERE NOT CORRECTLY ADDRESSED IN | | | THE PREVIOUS REVIEW. AN * AFTER THE COMMENTINDICATES | | | FURTHER EXPLANATION. | | | | | | 1} DUE TO THE METER LOCATION, A DISCONNECT IS REQUIRED | | | PER 230.70, 225.32. INDICATE LOCATION ON PLAN PER | | | 230.70(A)(1)* THE DISCONNECT ON THE PLAN WAS NOT | | | INCLUDED IN THE RISER DIAGRAM.SHOW EQUIPMENT GROUND | | | WHERE REQUIRED (ON THE LOAD SIDE OF THE DISCONNECT) AND | | | SIZE SAME PER 250.122. | | | | | | 4} THE DINING ROOM RECEPTACLE CIRCUIT #27, MUST BE A 20 | | | AMP CIRCUIT PER 210.52(B)(1). * THE DESIGNER HAS LEFT A | | | # 14 CONDUCTOR ON A 20 AMP CIRCUIT BREAKER IN VIOLATION | | | OF 310.16, AND THE CIRCUIT RATED AT 543 (KVA?) WHEN PER | | | 220.52(A) IT MUST BE 1500 VA. NOTE: ALL RATINGS ARE | | | INCORRECTLY NOTED AS KVA PER THE HEADING OF THAT | | | COLUMN. | | | | | | 6} THE DISCONNECTING MEANS LOCATED AT THE A/C EQUIPMENT | | | (BOTH UNITS) DO NOT INDICATE COMPLIANCE WITH THE | | | CLEARANCE REQUIREMENTS OF 110.26.* NOT ADDRESSED. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW. | | | CITY OF WEST PALM BEACH | | | 561/805-6718 |
|