2007-10-18 17:42:032004 FBC WITH 2006 AMENDMENTS
 NEW SFR
 CBS CONSTRUCTION
  
 DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED. SUBMIT PLANS
 WITH ORIGINAL COUNTY STAMP AND COPY OF PAID IMPACT FEE
 RECEIPT.
  
 3) SUBMIT MANUFACTURER'S SPECIFICATIONS, PRODUCT
 APPROVAL OR TECHNICAL BULLETIN SHOWING THAT THE SIMPSON
 HUS 28 CAN BE ATTACHED TO CONCRETE OR MASONRY WITH
 TITEN SCREWS OR SPECIFY ANOTHER CONNECTOR.
  
 4)WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL. THE PRODUCT APPROVALS FOR
 THE ASPHALT ROOF SHINGLES HAVE NOT BEEN APPROVED IN
 WRITING BY THE DESIGNER OF RECORD.
  
 5) SUBMIT PRODUCT APPROVALS FOR THE EXTERIOR OUTSWING
 DOOR AT THE CARPORT AS REQUIRED BY FAC RULE 9B-72. IF
 IT IS THE SAME AS THE FRONT DOOR, PLEASE INDICATE ON
 THE FRONT DOOR PRODUCT APPROVAL.
  
 6) THE PRODUCT APPROVAL FOR THE TAMKO ROOFING HAS BEEN
 REMOVED FROM THE SUBMITTAL. HOWEVER, IT IS STILL LISTED
 ON SHEET 1 OF THE PLANS AND SIGNED AND SEALED RAS 117
 CALCULATIONS FOR ENHANCED FASTENING FROM THE ENGINEER
 WERE SUBMITTED. PLEASE CLARIFY.
  
 7) THE PRODUCT APPROVAL NOA FOR THE RIDGE VENT LIMITS
 IT TO A MINIMUM SLOPE OF 3 :12. THE PLANS SPECIFY A
 ROOF PITCH OF 2.5 : 12. PLEASE CORRECT.
  
 8) SHEET 4 OF THE PLANS HAS WHITE-OUT AND A LABEL TAPED
 TO THE PLANS CHANGING THE ROOFING MATERIAL. THIS IS NOT
 ALLOWED BY FBC 106.1.3 OF THE CITY AMENDMENTS. PLEASE
 CORRECT.
  
 9) ASPHALT SINGLES ARE DESIGNED TO BE USED ON A SLOPED
 ROOF THAT ALLOWS THE RAIN WATER TO FLOW DIRECTLY OFF OF
 IT. THE INSTALLATION OF ASPHALT SHINGLES WITH THE ROOF
 SLOPING INTO THE PARAPET WALLS WILL CAUSE THE RAIN
 WATER TO BACK UP UNDER THE SHINGLES. THIS IS A VERY BAD
 DESIGN. SUBMIT A ROOFING APPLICATION STANDARD,
 MANUFACTURER'S INSTALLATION INSTRUCTIONS OR
 SPECIFICATIONS THAT ALLOWS THE SINGLES TO BE INSTALLED
 IN THIS WAY.
  
 10) PLEASE PROVIDE CLARIFICATION AS TO HOW THE ROOF
 TRUSSES WILL BE ATTACHED AT THE EXTERIOR WALLS AND HOW
 THEY WILL BE SUPPORTED. IS THERE A 2 X PT WALL LEDGER
 WITH THE TRUSS HANGERS MOUNTED TO IT? THE SCUPPER
 DETAILS SHOW THE ENDS OF THE TRUSSES EXTENDING INTO THE
 EXTERIOR WALLS.
  
 11) PLEASE DO NOT STAPLE THE PRODUCT APPROVALS TO THE
 PLANS.
  