| 2008-09-03 16:40:34 | PLUMBING PLAN REVIEW: |
| | REVISION DENIED: |
| | |
| | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. |
| | |
| | 1. SHEET 1 SANITARY RISER: PLEASE CORRECT THE FOLLOWING |
| | PER THE FBC-2004 PLUMBING CODE SECTIONS. |
| | |
| | A} THERE IS A 3 INCH HORIZONTAL DRY VENT BEING |
| | INDICATED UPSTREAM OF THE WATER CLOSET. HORIZONTAL DRY |
| | VENTS ARE NOT ALLOWED. PER SECTION 905.3 VENT |
| | CONNECTION TO DRAINAGE SYSTEM. |
| | |
| | B} LAVATORY NEEDS A VENT AND A WATER-SEAL TRAP. PER |
| | SECTION 901.2.1 VENTING REQUIRED AND SECTION 1002.1 |
| | FIXTURE TRAP. |
| | NOTE: IF A 1-1/4" TRAP IS USED ON THE LAVATORY A |
| | CLEANOUT IS REQUIRED AT THE BASE OF ITS STACK (SECTION |
| | 708.3.4 BASE OF STACK), HOWEVER IF A 1-1/2" TRAP IS |
| | USED PER 708.7 MINIMUM SIZE EXCEPTION (1) A CLEANOUT IS |
| | NOT REQUIRED. |
| | |
| | C} THE 3 INCH HORIZONTAL BRANCH AND STACK IS NOT |
| | CLEARLY IDENTIFIED. IS THIS FOR THE WASHING MACHINE? |
| | PLEASE CLARIFY THIS AND PROVIDE THE FOLLOWING FOR THE |
| | WASHING MACHINE. |
| | *SECTION 406.3 WASTE CONNECTIONS.THE TRAP AND |
| | FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES |
| | WASHER SHALL BE A MINIMUM OF 2 INCHES |
| | (51MM) IN DIAMETER. THE AUTOMATIC |
| | CLOTHES WASHER FIXTURE DRAIN SHALL |
| | CONNECT TO A BRANCH DRAIN OR DRAINAGE |
| | STACK A MINIMUM OF 3 INCHES (76MM) IN |
| | DIAMETER. |
| | |
| | *SECTION 802.4 STANDPIPES.STANDPIPES SHALL BE |
| | INDIVIDUALLY TRAPPED. STANDPIPES SHALL |
| | EXTEND A MINIMUM OF 18 INCHES (457MM) |
| | AND A MAXIMUM OF 42 INCHES (1066MM) |
| | ABOVE THE TRAP WEIR. ACCESS SHALL BE |
| | PROVIDED TO ALL STANDPIPES AND DRAINS |
| | FOR RODDING. |
| | |
| | *SECTION 708.7 MINIMUM SIZE. CLEANOUTS SHALL |
| | BE THE SAME NOMINAL SIZE AS THE PIPE |
| | THEY SERVE UP TO 4 INCHES (102MM). |
| | CLEANOUT FOR THE WASHING MACHINE SHALL BE 3 INCH. |
| | |
| | *SECTION 708.9 ACCESS. ACCESS SHALL BE PROVIDED TO ALL |
| | CLEANOUTS. CLEANOUT FOR THE WASHING MACHINE SHALL BE |
| | LOCATED AT FOUR FEET ABOVE FINNISH FLOOR (4' A.F.F.). |
| | |
| | D} CLEARLY INDICATE A TWO-WAY CLEANOUT AT THE JUNCTION |
| | OF THE BUILDING DRAIN AND BUILDING SEWER. PER SECTION |
| | 708.3.5 BUILDING DRAIN AND BUILDING SEWER JUNCTION. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE |
| | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW |
| | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | NOTE: PLEASE REFERENCE THE EXAMPLE SANITARY ISOMETRIC |
| | RISER DIAGRAM THAT REFLECTS THE FLOOR PLAN AND IS CODE |
| | COMPLIANT TO HELP IN THE REVISON ATTACHED TO THESE |
| | PLUMBING COMMENTS. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY: MIKE PERSON |
| | PLUMBING PLANS EXAMINER |