| Plan Review Notes For Permit 07070599 |
| Permit Number |
07070599 |
|
| Review Stop |
M |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2008-09-04 09:54:23 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | | (F.S.). | | | | | | REVISION TO PLANS | | | *** DENIED *** | | | | | | 1) PAGE 1 OF 2 FLOOR PLAN SHOWS AN A/C GRILL IN THE | | | STUDY (SEE YELLOW HIGH LIGHT ON PLAN) PLEASE STATE IF | | | GRILL IS SUPPLY, RETURN, SHOW SIZE. CFM'S. AND PROVIDE | | | THE DUCT (FLEX) INFORMATION, PER 2004 WPB | | | AMEND.106.3.5.4 (10). | | | | | | 2) PLAN SHOWS AN A/C GRILL IN THE BATHROOM, PLEASE SEE | | | NOTE ABOVE. | | | | | | 3) SHOW THE CFM'S AT THE BATHROOM EXHAUST FAN, PER 2004 | | | FBC/R M1506.3. | | | | | | 4) STATE ON PLAN WHERE THE BATHROOM EXHAUST FAN WILL | | | TERMINATE, PER 2004 FBC/R M1506.2. | | | | | | 5) PLAN STATES "EXISTING DOOR TO STUDY A/C RETURN" IF | | | THE DOOR IS TO BE USED AS A RETURN IT MUST BE LOUVERED | | | OR HAVE A TRANSFER GRILL INSTALLED (IF GRILL SHOW SIZE) | | | STATE ON PLAN WHICH IS BEING USED, PER 2004 FBC/R | | | M1602.4. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|