2008-09-04 09:54:23PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 REVISION TO PLANS
 *** DENIED ***
  
 1) PAGE 1 OF 2 FLOOR PLAN SHOWS AN A/C GRILL IN THE
 STUDY (SEE YELLOW HIGH LIGHT ON PLAN) PLEASE STATE IF
 GRILL IS SUPPLY, RETURN, SHOW SIZE. CFM'S. AND PROVIDE
 THE DUCT (FLEX) INFORMATION, PER 2004 WPB
 AMEND.106.3.5.4 (10).
  
 2) PLAN SHOWS AN A/C GRILL IN THE BATHROOM, PLEASE SEE
 NOTE ABOVE.
  
 3) SHOW THE CFM'S AT THE BATHROOM EXHAUST FAN, PER 2004
 FBC/R M1506.3.
  
 4) STATE ON PLAN WHERE THE BATHROOM EXHAUST FAN WILL
 TERMINATE, PER 2004 FBC/R M1506.2.
  
 5) PLAN STATES "EXISTING DOOR TO STUDY A/C RETURN" IF
 THE DOOR IS TO BE USED AS A RETURN IT MUST BE LOUVERED
 OR HAVE A TRANSFER GRILL INSTALLED (IF GRILL SHOW SIZE)
 STATE ON PLAN WHICH IS BEING USED, PER 2004 FBC/R
 M1602.4.
  