| 2008-07-08 13:20:59 | PLUMBING PLAN REVIEW: |
| | DENIED 3RD TIME: |
| | |
| | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | 1. SHEET 1, SANITARY ISOMETRIC RISER DIAGRAM: PLEASE |
| | CORRECT THE FOLLOWING PER FBC-2004 PLUMBING SECTIONS. |
| | |
| | |
| | A} SECTION 701.1 SCOPE, 901.1 SCOPE, AND (W.P.B. AS |
| | AMENDED) 106.3.5.4 (9) PLUMBING: CLEARLY INDICATE THE |
| | SIZES TO ALL WASTE, VENTS AND WATER-SEAL TRAPS. THE |
| | ONLY SIZE PIPING BEING INDICATED ON THE PLANS IS 3 INCH |
| | BY THE CLEANOUT AND 3" VTR. IS IT THE INTENT TO HAVE |
| | ALL WASTE PIPING 3 INCH? |
| | |
| | B} SECTION 905.3 VENT CONNECTION TO DRAINAGE SYSTEM, |
| | NO HORIZONTAL DRY VENTS ARE ALLOWED (DRY VENT BETWEEN |
| | SHOWER AND VENT THRU ROOF NOT ALLOWED). |
| | |
| | C} SECTION 901.2.1 VENTING REQUIRED, THE WASHING |
| | MACHINE AND LAVATORY REQUIRE A VENT. |
| | |
| | D} SECTION 1002.3 PROHIBITED TRAPS, THE LAVATORY IS |
| | INDICATING A "S" TRAP WHICH IS PROHIBITED. |
| | |
| | E} SECTION 701.1 SCOPE, PLANS DO NOT CLEARLY INDICATE |
| | THAT THE PROPOSED BATHROOM SANITARY SYSTEM WILL TIE |
| | INTO THE EXISTING. |
| | |
| | F} SECTION 708.3.5 BUILDING DRAIN AND BUILDING SEWER |
| | JUNCTION, CLEARLY INDICATE THE CLEANOUT AT THE JUNCTION |
| | OF THE BUILDING DRAIN AND BUILDING SEWER AS BEING A |
| | TWO-WAY CLEANOUT. |
| | |
| | G} SECTION 405.3.1 WATER CLOSETS, URINALS, LAVATORIES, |
| | AND BIDETS. A WATER CLOSET, URINAL, LAVATORY OR BIDET |
| | SHALL NOT BE SET CLOSER THAN 15 INCHES (381 MM) FROM |
| | ITS CENTER TO ANY SIDE WALL, PARTITION, VANITY OR OTHER |
| | OBSTRUCTION, OR CLOSER THAN 30 INCHES (762 MM) |
| | CENTER-TO-CENTER BETWEEN WATER CLOSETS, URINALS OR |
| | ADJACENT FIXTURES. THERE SHALL BE AT LEAST A 21-INCH |
| | (533 MM) CLEARANCE IN FRONT OF THE WATER CLOSET, URINAL |
| | OR BIDET TO ANY WALL, FIXTURE OR DOOR. WATER CLOSET |
| | COMPARTMENTS SHALL NOT BE LESS THAN 30 INCHES (762 MM) |
| | WIDE OR 60 INCHES (1524 MM) DEEP. THERE SHALL BE AT |
| | LEAST A 21-INCH (533 MM) CLEARANCE IN FRONT OF A |
| | LAVATORY TO ANY WALL, FIXTURE OR DOOR (SEE FIGURE |
| | 405.3.1 ). |
| | NOTE: THE LAVATORY IS NOT COMPLIANT. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE |
| | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW |
| | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | END OF COMMENTS: |
| | |