2008-01-17 15:00:38PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT
 ALSO, PER 2004 FBC 13-600.3.ABC.2. (PLEASE SUBMIT 2
 COPY'S).
  
 2) WAS UNABLE TO FIND THE ALEN AMS09 DUCTLESS
 MINI-SPLIT A/C SYSTEM ON THE ARI DIRECTORY WEB-SITE.
 PLEASE SUBMIT THE ARI CERTIFICATE, SEE 2004 FBC
 13-607.1.ABC.3.1.1.
  
 3) PLEASE ADD AN A/C SCHEDULE WITH THE PERTINENT
 INFORMATION TO THE MECHANICAL PLAN, SEE 2004 WPB AMEND.
 106.3.5.4 (10).
  
 4) PLEASE SUBMIT DETAILED MANUFACTURER'S
 SPECIFICATION'S AND INSTALLATION INSTRUCTIONS FOR THE
 A/C SYSTEM.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]