| Plan Review Notes For Permit 07070599 |
| Permit Number |
07070599 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2008-01-17 15:00:38 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | | (F.S.). | | | | | | *** DENIED *** | | | 1) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT | | | ALSO, PER 2004 FBC 13-600.3.ABC.2. (PLEASE SUBMIT 2 | | | COPY'S). | | | | | | 2) WAS UNABLE TO FIND THE ALEN AMS09 DUCTLESS | | | MINI-SPLIT A/C SYSTEM ON THE ARI DIRECTORY WEB-SITE. | | | PLEASE SUBMIT THE ARI CERTIFICATE, SEE 2004 FBC | | | 13-607.1.ABC.3.1.1. | | | | | | 3) PLEASE ADD AN A/C SCHEDULE WITH THE PERTINENT | | | INFORMATION TO THE MECHANICAL PLAN, SEE 2004 WPB AMEND. | | | 106.3.5.4 (10). | | | | | | 4) PLEASE SUBMIT DETAILED MANUFACTURER'S | | | SPECIFICATION'S AND INSTALLATION INSTRUCTIONS FOR THE | | | A/C SYSTEM. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|