| 2008-01-29 07:16:26 | DENIED BY BUILDING |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT |
| | MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 3) SUBMIT ENERGY CALCULATIONS FOR THE ENCLOSED GARAGE |
| | AS REQUIRED BY FBC CHAPTER 13. TWO COPIES ARE REQUIRED. |
| | THE WRONG FORMS WERE SUBMITTED. THE FORM FOR SOUTH |
| | CLIMATE ZONES 7,8 AND 9 IS REQUIRED. THE CITY OF WEST |
| | PALM BEACH IS LOCATED IN CLIMATE ZONE 8. THE |
| | OWNER/AGENT IS REQUIRED TO SIGN AND DATE THE ENERGY |
| | CALCULATION FORMS. SEE FBC SECTION 13-6. |
| | |
| | 4) SHOW COMPLIANCE WITH R404.1.6 HEIGHT ABOVE FINISHED |
| | GRADE. |
| | CONCRETE AND MASONRY FOUNDATION WALLS SHALL EXTEND |
| | ABOVE THE FINISHED GRADE ADJACENT TO THE FOUNDATION AT |
| | ALL POINTS A MINIMUM OF 4 INCHES (102 MM) WHERE MASONRY |
| | VENEER IS USED AND A MINIMUM OF 6 INCHES (152 MM) |
| | ELSEWHERE. ALSO SEE SECTION 704 INSPECTION FOR |
| | TERMITES. |
| | IN ORDER TO PROVIDE FOR INSPECTION FOR TERMITE |
| | INFESTATION, CLEARANCE BETWEEN EXTERIOR WALL COVERINGS |
| | AND FINAL EARTH GRADE ON THE EXTERIOR OF A BUILDING |
| | SHALL NOT BE LESS THAN 6 INCHES (152 MM). EXCEPTIONS: |
| | 1.PAINT OR DECORATIVE CEMENTITIOUS FINISH LESS |
| | THAN 5 / 8 INCH (17.1 MM) THICK ADHERED DIRECTLY TO THE |
| | MASONRY FOUNDATION SIDEWALL. |
| | 2.ACCESS OR VEHICLE RAMPS WHICH RISE TO THE |
| | INTERIOR FINISH FLOOR ELEVATION FOR THE WIDTH OF SUCH |
| | RAMPS ONLY. |
| | 3.A 4-INCH (102 MM) INSPECTION SPACE ABOVE PATIO |
| | AND GARAGE SLABS AND ENTRY AREAS. |
| | 4.IF THE PATIO HAS BEEN SOIL TREATED FOR TERMITES, |
| | THE FINISH ELEVATION MAY MATCH THE BUILDING INTERIOR |
| | FINISH FLOOR ELEVATIONS ON MASONRY CONSTRUCTION ONLY. |
| | 5.MASONRY VENEERS. |
| | A CONCRETE CURB UNDER THE FRAME WALL OR OTHER |
| | ACCEPTABLE METHOD COULD BE USED AT THE GARAGE DOOR |
| | OPENING OR IT COULD BE ENCLOSED WITH MASONRY. |
| | |
| | 5) SHOW COMPLIANCE WITH R506.2.3 VAPOR RETARDER. A 6 |
| | MIL (0.006 INCH; 152 UM) POLYETHYLENE OR APPROVED VAPOR |
| | RETARDER WITH JOINTS LAPPED NOT LESS THAN 6 INCHES (152 |
| | MM) SHALL BE PLACED BETWEEN THE CONCRETE FLOOR SLAB AND |
| | THE BASE COURSE OR THE PREPARED SUBGRADE WHERE NO BASE |
| | COURSE EXISTS. THE CODE DOES NOT REQUIRE THIS IN |
| | GARAGES OR UNHEATED ACCESSORY STRUCTURES. HOWEVER, THIS |
| | AREA IS BEING CONVERTED TO LIVING SPACE WHICH DOES |
| | REQUIRE A VAPOR RETARDER. NOTE: THE EXISTING CONCRETE |
| | CAN SEALED WITH AN APPROVED WATER PROOFING. SPECIFY ON |
| | THE PLANS. |
| | |
| | 6) PROVIDE A SECTION OF THE EXTERIOR WALL AT THE |
| | IN-FILL FRAMING AT THE GARAGE DOOR OPENING. SHOW THE |
| | HEIGHT OF THE FINISH FLOOR ABOVE GRADE, THE CEILING |
| | HEIGHT AND FINISH, SPECIFY THE INTERIOR AND EXTERIOR |
| | WALL COVERINGS, VAPOR BARRIERS, INSULATION,FRAMING |
| | CONNECTORS, FASTENERS, ANCHORS ETC.FBC 106.1.2 |
| | |
| | 7)SHOW COMPLIANCE WITH R310 FOR EMERGENCY ESCAPE AND |
| | RESCUE OPENINGS REQUIRED FOR SLEEPING ROOMS. WINDOWS |
| | SPECIFIED ON THE PLAN DO NOT COMPLY WITH THE REQUIRED |
| | CLEAR OPENING. R310.1 EMERGENCY ESCAPE AND RESCUE |
| | REQUIRED. |
| | BASEMENTS WITH HABITABLE SPACE AND EVERY SLEEPING ROOM |
| | SHALL HAVE AT LEAST ONE OPENABLE EMERGENCY ESCAPE AND |
| | RESCUE OPENING. WHERE BASEMENTS CONTAIN ONE OR MORE |
| | SLEEPING ROOMS, EMERGENCY EGRESS AND RESCUE OPENINGS |
| | SHALL BE REQUIRED IN EACH SLEEPING ROOM, BUT SHALL NOT |
| | BE REQUIRED IN ADJOINING AREAS OF THE BASEMENT. WHERE |
| | EMERGENCY ESCAPE AND RESCUE OPENINGS ARE PROVIDED THEY |
| | SHALL HAVE A SILL HEIGHT OF NOT MORE THAN 44 INCHES |
| | (1118 MM) ABOVE THE FLOOR. WHERE A DOOR OPENING HAVING |
| | A THRESHOLD BELOW THE ADJACENT GROUND ELEVATION SERVES |
| | AS AN EMERGENCY ESCAPE AND RESCUE OPENING AND IS |
| | PROVIDED WITH A BULKHEAD ENCLOSURE, THE BULKHEAD |
| | ENCLOSURE SHALL COMPLY WITH SECTION 310.3 . THE NET |
| | CLEAR OPENING DIMENSIONS REQUIRED BY THIS SECTION SHALL |
| | BE OBTAINED BY THE NORMAL OPERATION OF THE EMERGENCY |
| | ESCAPE AND RESCUE OPENING FROM THE INSIDE. EMERGENCY |
| | ESCAPE AND RESCUE OPENINGS WITH A FINISHED SILL HEIGHT |
| | BELOW THE ADJACENT GROUND ELEVATION SHALL BE PROVIDED |
| | WITH A WINDOW WELL IN ACCORDANCE WITH SECTION R310.2 . |
| | THE EMERGENCY ESCAPE AND RESCUE OPENING SHALL BE |
| | PERMITTED TO OPEN INTO A SCREEN ENCLOSURE, OPEN TO THE |
| | ATMOSPHERE, WHERE A SCREEN DOOR IS PROVIDED LEADING |
| | AWAY FROM THE RESIDENCE. |
| | R310.1.1 MINIMUM OPENING AREA. |
| | ALL EMERGENCY ESCAPE AND RESCUE OPENINGS SHALL HAVE A |
| | MINIMUM NET CLEAR OPENING OF 5.7 SQUARE FEET (0.530 M 2 |
| | ). |
| | EXCEPTION: GRADE FLOOR OPENINGS SHALL HAVE A MINIMUM |
| | NET CLEAR OPENING OF 5 SQUARE FEET (0.465 M 2 ). |
| | R310.1.2 MINIMUM OPENING HEIGHT. |
| | THE MINIMUM NET CLEAR OPENING HEIGHT SHALL BE 24 INCHES |
| | (610 MM). |
| | R310.1.3 MINIMUM OPENING WIDTH. |
| | THE MINIMUM NET CLEAR OPENING WIDTH SHALL BE 20 INCHES |
| | (508 MM). |
| | |
| | 8) SUBMIT 2 COPIES OF PRODUCT APPROVALS FOR THE |
| | EXTERIOR WINDOWS AND STORM PANELS (IF WINDOWS ARE NOT |
| | IMPACT RATED). SPECIFYTHE MOUNT TYPE, ANCHOR TYPE AND |
| | ANCHOR SPACING FOR THE STORM PANELS. CIRCLE THE |
| | APPROPRIATE INFORMATION ON THE PRODUCT APPROVAL |
| | DRAWINGS AND TABLES. |
| | |
| | 9)PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. |
| | |
| | 10)FBC 106.3* CITY AMENDMENTS PRODUCT |
| | APPROVALS. THOSE PRODUCT WHICH ARE |
| | REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| | FOR JURISDICTIONAL APPROVAL. THIS APPLIES TO THE WINDOW |
| | AND STORM PANEL PRODUCT APPROVALS. |
| | |
| | 11) ON SHEET 1 THERE IS A NOTE BELOW THE FLOOR PLAN |
| | THAT STATES ADD 6" BATT INSULATION IN THE CEILING. ALSO |
| | ON SHEET 1, THE INTERIOR WALL SECTION SPECIFIES 9" |
| | (R30) BATT INSULATION. PLEASE CORRECT. |
| | |
| | 12) ADDRESS COMMENTS OF OTHER TRADES. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |