| Notes |
| Date |
Text |
| 2007-08-02 11:14:37 | DENIED; | | | 1. SANITARY RISER DIAGRAM; | | | A) AUTOMATIC CLOTHES WASHER SHALL DISCHARGE | | | DOWN STREAM OF THE BATHROOM GROUP. SEE FBC-2004 | | | PLUMBING SECTION 909.1. | | | B) SHOW TRAPS ON LAVATORY AND SHOWER. | | | C) HORIZONTAL DRY VENTS ARE NOT PERMITTED. | | | SEC905.3 | | | 2. THERE MUST BE 21" IN FRONT OF THE LAVATORY. SEE | | | SECTION 405.3.1. | | | 3. THE LINE BETWEEN THE TOILET AND THE WATER HEATER, IS | | | THAT A WALL? IF SO ACCESS IS REQUIRED TO HEATER IF NOT | | | IF ELECTRICMUST BE A GFI , IF GAS IT IS NOT PERMITED | | | IN BATHROOM. PLEASE CLARIFY. | | | 4. SHOWER REQUIRES A CURB ON OPEN SIDES, NOT SHOWN. IF | | | INCLOSED SHOW DOOR. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|