| Plan Review Notes For Permit 07070599 |
| Permit Number |
07070599 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-07-27 10:00:02 | *** DENIED *** | | | 1) THE ENGINEER WHO SEALED THE PLANS MUST ALSO HAVE | | | THEIR PRINTED NAME AND LICENSE NUMBER IN THE TITLE | | | BLOCK, SEE FAC 61G-15-23.002, PLEASE CORRECT. | | | | | | 2) PLEASE SUBMIT ENERGY CALCULATIONS, SEE 2004 FBC | | | 13-101.2.2. | | | | | | 3) PLANS NOTE ADD 6" BATT INSULATION IN CEILING, PLEASE | | | ADD WHAT THE R-VALUE WILL BE. | | | | | | 4) PLEASE STATE ON PLANSIF THE EXISTING WATER HEATER | | | IS GAS OR ELECTRIC, AND SHOW HOW IT WILL BE ACCESSED. | | | | | | 5) MECHANICAL PERMIT #07070601 HAS BEEN APPLIED FOR AND | | | APPLICATION STATES EXTEND A/C, PLEASE SUBMIT MECHANICAL | | | PLAN FOR REVIEW, SEE 2004 FBC CITY OF WPB AMEND. | | | 106.3.5.4 #10. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|