Plan Review Notes
Plan Review Notes For Permit 07070599
Permit Number 07070599
Review Stop B
Sequence Number 1
Notes
Date Text
2007-08-01 18:26:28DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) SUBMIT ENERGY CALCULATIONS FOR THE ENCLOSED GARAGE
 AS REQUIRED BY FBC CHAPTER 13.
  
 4) PROVIDE EXTERIOR ELEVATIONS OF THE ENCLOSED GARAGE.
  
  
 5) SPECIFY THE WIND DESIGN DATA ON THE PLANS AS
 REQUIRED BY FBC 1603.1.4. THE BASIC WINDSPEED, THE
 IMPORTANCE FACTOR,COMPONENT AND CLADDING PRESSURES,
 ETC.
  
 6) SPECIFY THE LEVEL OF ALTERATION ON THE PLANS. SEE
 FBC EXISTING BUILDING CODE CHAPTER 3.
  
 7) SPECIFY THE CURRENT CODE EDITION ON THE PLANS.
  
 8) SHOW COMPLIANCE WITH R404.1.6 HEIGHT ABOVE FINISHED
 GRADE.
 CONCRETE AND MASONRY FOUNDATION WALLS SHALL EXTEND
 ABOVE THE FINISHED GRADE ADJACENT TO THE FOUNDATION AT
 ALL POINTS A MINIMUM OF 4 INCHES (102 MM) WHERE MASONRY
 VENEER IS USED AND A MINIMUM OF 6 INCHES (152 MM)
 ELSEWHERE.
  
 9) SHOW COMPLIANCE WITH R320.1TERMITE PROTECTION SHALL
 BE PROVIDED BY REGISTERED TERMITICIDES, INCLUDING SOIL
 APPLIED PESTICIDES, BAITING SYSTEMS, AND PESTICIDES
 APPLIED TO WOOD, OR OTHER APPROVED METHODS OF TERMITE
 PROTECTION LABELED FOR USE AS A PREVENTATIVE TREATMENT
 TO NEW CONSTRUCTION (SEE SECTION 202 , REGISTERED
 TERMITICIDE). UPON COMPLETION OF THE APPLICATION OF THE
 TERMITE PROTECTIVE TREATMENT, A CERTIFICATE OF
 COMPLIANCE SHALL BE ISSUED TO THE BUILDING DEPARTMENT
 BY THE LICENSED PEST CONTROL COMPANY THAT CONTAINS THE
 FOLLOWING STATEMENT: ?THE BUILDING HAS RECEIVED A
 COMPLETE TREATMENT FOR THE PREVENTION OF SUBTERRANEAN
 TERMITES. TREATMENT IS IN ACCORDANCE WITH RULES AND
 LAWS ESTABLISHED BY THE FLORIDA DEPARTMENT OF
 AGRICULTURE AND CONSUMER SERVICES.?
  
 10) SHOW COMPLIANCE WITH R506.2.3 VAPOR RETARDER. A 6
 MIL (0.006 INCH; 152 ?M) POLYETHYLENE OR APPROVED VAPOR
 RETARDER WITH JOINTS LAPPED NOT LESS THAN 6 INCHES (152
 MM) SHALL BE PLACED BETWEEN THE CONCRETE FLOOR SLAB AND
 THE BASE COURSE OR THE PREPARED SUBGRADE WHERE NO BASE
 COURSE EXISTS.
  
 11) SHOW COMPLIANCE WITH R806.1 VENTILATION REQUIRED.
 ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES FORMED WHERE
 CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF
 RAFTERS SHALL HAVE CROSS VENTILATION FOR EACH SEPARATE
 SPACE BY VENTILATING OPENINGS PROTECTED AGAINST THE
 ENTRANCE OF RAIN. VENTILATING OPENINGS SHALL BE
 PROVIDED WITH CORROSION-RESISTANT WIRE MESH, WIT H 1 /
 8 INCH (3.2 MM) MINIMUM TO ? INCH (6.4 MM) MAXIMUM
 OPENINGS.
  
 12) SHOW COMPLIANCE WITH R807.1 ATTIC ACCESS.THE
 ROUGH-FRAMED OPENING SHALL NOT BE LESS THAN 22 INCHES
 BY 30 INCHES (559 MM BY 762 MM) AND SHALL BE LOCATED IN
 A HALLWAY OR OTHER READILY ACCESSIBLE LOCATION. A
 30-INCH (762 MM) MINIMUM UNOBSTRUCTED HEADROOM IN THE
 ATTIC SPACE SHALL BE PROVIDED AT SOME POINT ABOVE THE
 ACCESS OPENING. SEE SECTION M1305.1.3 FOR ACCESS
 REQUIREMENTS WHERE MECHANICAL EQUIPMENT IS LOCATED IN
 ATTICS.
  
 13) PROVIDE A SECTION OF THE EXTERIOR WALL AT THE
 IN-FILL FRAMING AT THE GARAGE DOOR OPENING. SHOW THE
 HEIGHT OF THE FINISH FLOOR ABOVE GRADE, THE CEILING
 HEIGHT AND FINISH, SPECIFY THE INTERIOR AND EXTERIOR
 WALL COVERINGS, VAPOR BARRIERS, INSULATION,FRAMING
 CONNECTORS, FASTENERS, ANCHORS ETC.FBC 106.1.2
  
 14)THERE IS A TYPICAL WALL SECTION ON THE PLANS.
 PLEASE INDICATE IF THIS IS AN INTERIOR LOAD BEARING OR
 NON LOAD BEARING WALL. SPECIFY THE LENGTH/EMBED DEPTH
 OF THE RED HEAD ANCHORS.
  
 15) SPECIFY THE WINDOW TYPES (IE SINGLE HUNG, CASEMENT,
 ETC.) AND SPECIFY THE REQUIRED OPENING PRESSURES.
  
 16)SHOW COMPLIANCE WITH R310 FOR EMERGENCY ESCAPE AND
 RESCUE OPENINGS REQUIRED FOR SLEEPING ROOMS.
  
 17) SUBMIT PRODUCT APPROVALS FOR THE EXTERIOR WINDOWS
 AND STORM PANELS (IF WINDOWS ARE NOT IMPACT RATED).
 SPECIFYTHE MOUNT TYPE, ANCHOR TYPE AND ANCHOR SPACING
 FOR THE STORM PANELS.
  
 18)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE.
  
 19)WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 20) ADDRESS COMMENTS OF OTHER TRADES.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  
  
  
  
  
  
  
  
  