| Date |
Text |
| 2007-08-06 10:02:46 | DENIED |
| | REFERENCE: |
| | ** FBC-2004 SECTION 424.2 OR R4101 SWIMMING POOLS. |
| | ** FBC-2004 PLUMBING. |
| | ** FBC-2004 CHAPTER 1, THE CITY OF |
| | WEST PALM BEACH AMENDMENTS. |
| | ** FLORIDA ADMINISTRATIVE CODE. |
| | ** FLORIDA STATUTES. |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE: |
| | |
| | 1. PLEASE CORRELATE THE SPA SPECIFICATIONS WITH THE |
| | SPA PLANS ON THE RESUBMITTAL. SPA SPECIFICATIONS ARE |
| | INDICATING 7 THERAPY JETS AND THE SPA PLANIS |
| | INDICATING 6 THERAPY JETS. |
| | |
| | 2. FBC-2004 SEC. 424.2.6.6.5, OR |
| | FBCR-2004 SEC. R4101.6.6.5 WHERE |
| | PROVIDED, THE VACUUM OR PRESSURE CLEANER |
| | FITTING SHALL BE LOCATED AT LEAST 6" AND |
| | NOT GREATER THAN 12" BELOW THE MINIMUM |
| | OPERATING WATER LEVEL OR AS AN |
| | ATTACHMENT TO THE SKIMMER. |
| | NOTE: DETAIL REQUIRED WITH MAKE AND MODEL NUMBER OF THE |
| | FITTING. |
| | |
| | 3. FBC-2004 SEC. 424.2.9, OR FBCR-2004 SEC. |
| | R4101.9 WATER SUPPLY, LOCAL ORD. |
| | #2853-95, BACKFLOW REQUIRED ON WATER |
| | SERVICE.(PLEASE ADD TO NOTES ON THE RESUBMITTAL) |
| | |
| | 4. FBC-2004 SEC. 424.2.12.1, OR |
| | FBCR-2004 SEC. R4101.12.1 PRESSURE |
| | TESTS. PER MANUFACTURE RECOMMENDATIONS, |
| | NO AIR TEST SHALL BE APPROVED FOR PVC |
| | PIPE AND FITTINGS. (PLEASE ADD TO NOTES ON THE |
| | RESUBMITTAL) |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY MIKE PERSON |
| | PLUMBING PLANS EXAMINER |
| | (561) 805-6730 |
| | FAX (561) 805-6731 |
| | E-MAIL= [email protected] |
| | |
| | |