Plan Review Notes
Plan Review Notes For Permit 07070569
Permit Number 07070569
Review Stop B
Sequence Number 5
Notes
Date Text
2009-02-09 16:18:57BUILDING PLAN REVIEW
 PERMIT: 07070569
 ADD: 7101 S. DIXIE HWY.
 CONT: JLV CONSTRUCTION SERVICES.
 TEL: (561)876-8539
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 2-9-09
 REVIEW: 2 REVISION: STAIRS.
 ACTION: DENIED
  
 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) OK
 3) OK
 4) OK
  
 5) NOTE: IF A NEW SET OF STAIRS, HANDRAIL AND GUARD
 RAIL IS BUILT, THEY WILL HAVE TO MEET THE REQUIREMENTS
 OF THE FBC SECTION 1009, 1012 AND 1607.7. IF THE STAIRS
 ARE NEWLY CONSTRUCTED, INDICATE THE TYPE OF MATERIALS
 USED TO CONSTRUCT THE STAIRS. THE DRAWINGS ALSO NEED TO
 SHOW THE HANDRAIL GRASPABILITY. IF THE HANDRAIL IS NOT
 CIRCULAR, IT SHALL HAVE A PERIMETER DIMENSION OF AT
 LEAST 4 INCHES AND NOT GREATER THAN 6.25 INCHES WITH A
 MAXIMUM CROSS-SECTION DIMENSION OF 2.25 INCHES FBC
 1009.11.3. SHOW COMPLIANCE. THE STAIRS, HANDRAIL AND
 GUARDRAIL MAY MAINTAIN THE EXISTING DESIGN IF THEY ARE
 PARTIALLY REPLACE. IF THEY ARE TO BE COMPLETELY REMOVED
 AND REPLACED, THEY SHALL MEET THE REQUIREMENTS OF NEW
 STAIRS AND THE SECTIONS MENTIONED ABOVE. GUARDS SHALL
 FORM A PROTECTIVE BARRIER NOT LESS THAN 42 INCHES.
 1012.2. OPEN GUARDS SHALL HAVE BALUSTERS OR ORNAMENTAL
 PATTERNS SUCH THAT A 4 INCH DIAMETER SPHERE CANNOT PASS
 THROUGH. 1012.3. INDICATE HOW THE 2X4 ARE CONNECTED TO
 THE NEW 1X6 BRACING. THE TYPICAL TOP RAIL DETAIL DO NOT
 MEET THE REQUIREMENTS OF SECTION 1009.11.3. SHOW
 COMPLIANCE.
  
 6) THE UNIFORM LIVE LOAD AND CONCENTRATED LOAD FOR THE
 STAIRS SHALL ALSO BE STATED PER TABLE 1607.1.
  
 7) FBC 106.1: THE NEW STAIRS SHALL BE DESIGN BY A
 REGISTERED PROFESSIONAL. THE DESIGN PROFESSIONAL SHALL
 HAVE HIS ORIGINAL SEAL, SIGNATURE AND DATE ON THE
 DRAWINGS AS REQUIRED BY FLORIDA STATUTES 471 FOR
 ENGINEERS AND 481 FOR ARCHITECTS. THE DRAWINGS SHALL
 CONTAIN A TITLE BLOCK PER 61G1-16.004. THE TITLE BLOCK
 IS MISSING ON THE PLANS.
  
 8) ALL DRAWINGS AND INFORMATION SUBMITTED AND BEING
 FILED FOR PUBLIC RECORD SHALL CONTAIN THE ORIGINAL
 SIGNATURE OF THE DESIGN PROFESSIONAL OR THE PERSON
 TAKING RESPONSIBILITY FOR THE INFORMATION; PHOTO COPY
 SEAL AND SIGNATURES ARE NOT ACCEPTABLE. THE BUILDING
 OFFICIAL MAY ESTABLISH THROUGH DEPARTMENTAL POLICY,
 STANDARDS FOR PLANS AND SPECIFICATIONS, IN ORDER TO
 PROVIDE CONFORMITY TO ITS RECORD RETENTION PROGRAM.
 106.1.3*
  
 NOTE: INDICATE THE ADDITIONAL COST OF THE STAIRS ON THE
 APPLICATION INCLUDING DESIGNER FEES. 108.3*
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]
  