2009-01-09 13:55:49BUILDING PLAN REVIEW
 PERMIT: 07070569
 ADD: 7101 S. DIXIE HWY.
 CONT: JLV CONSTRUCTION SERVICES.
 TEL: (561)876-8539
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 1-9-09
 REVIEW: REVISION: STAIRS.
 ACTION: DENIED
  
 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS. THIS INFORMATION
 SHALL BE SHOWN ON THE DRAWINGS.
  
 3) DUE TO FACT THAT THESE STAIRS ARE EXTERIOR STAIRS
 THEY SHALL BE DESIGN TO MEET THE WIND LOAD FOR WEST
 PALM BEACH WHICH IS 140 MPH. THE WIND DESIGN
 INFORMATION SHALL BE SHOWN ON THE PLANS FBC 1603.1.4.
  
 4) FBC 1009.3: THE GREATEST RISE HEIGHT WITHIN ANY
 FLIGHT OF STAIRS SHALL NOT EXCEED THE SMALLEST BY MORE
 THAN 3/8 INCH. STAIR RISER HEIGHTS SHALL BE 7 INCHES
 MAXIMUM AND 4 INCHES MINIMUM. STAIR TREAD DEPTHS SHALL
 BE 11 INCHES MINIMUM.
  
 5) NOTE: IF A NEW SET OF STAIRS, HANDRAIL AND GUARD
 RAIL IS BUILT, THEY WILL HAVE TO MEET THE REQUIREMENTS
 OF THE FBC SECTION 1009, 1012 AND 1607.7. IF THE STAIRS
 ARE NEWLY CONSTRUCTED, INDICATE THE TYPE OF MATERIALS
 USED TO CONSTRUCT THE STAIRS. THE DRAWINGS ALSO NEED TO
 SHOW THE HANDRAIL GRASPABILITY. IF THE HANDRAIL IS NOT
 CIRCULAR, IT SHALL HAVE A PERIMETER DIMENSION OF AT
 LEAST 4 INCHES AND NOT GREATER THAN 6.25 INCHES WITH A
 MAXIMUM CROSS-SECTION DIMENSION OF 2.25 INCHES FBC
 1009.11.3. SHOW COMPLIANCE. THE STAIRS, HANDRAIL AND
 GUARDRAIL MAY MAINTAIN THE EXISTING DESIGN IF THEY ARE
 PARTIALLY REPLACE. IF THEY ARE TO BE COMPLETELY REMOVED
 AND REPLACED, THEY SHALL MEET THE REQUIREMENTS OF NEW
 STAIRS AND THE SECTIONS MENTIONED ABOVE. GUARDS SHALL
 FORM A PROTECTIVE BARRIER NOT LESS THAN 42 INCHES.
 1012.2. OPEN GUARDS SHALL HAVE BALUSTERS OR ORNAMENTAL
 PATTERNS SUCH THAT A 4 INCH DIAMETER SPHERE CANNOT PASS
 THROUGH. 1012.3. INDICATE HOW THE 2X4 ARE CONNECTED TO
 THE NEW 1X6 BRACING.
  
 6) FBC 1607.7.1: THE HANDRAIL AND GUARD RAIL SHALL BE
 DESIGNED TO RESIST A LOAD OF 50 LBS WHEN APPLIED IN ANY
 DIRECTION. THE UNIFORM LIVE LOAD AND CONCENTRATED LOAD
 FOR THE STAIRS SHALL ALSO BE STATED PER TABLE 1607.1.
  
 7) FBC 106.1: THE NEW STAIRS SHALL BE DESIGN BY A
 REGISTERED PROFESSIONAL. THE DESIGN PROFESSIONAL SHALL
 HAVE HIS ORIGINAL SEAL, SIGNATURE AND DATE ON THE
 DRAWINGS AS REQUIRED BY FLORIDA STATUTES 471 FOR
 ENGINEERS AND 481 FOR ARCHITECTS. THE DRAWINGS SHALL
 CONTAIN A TITLE BLOCK PER 61G1-16.004.
  
 8) ALL DRAWINGS AND INFORMATION SUBMITTED AND BEING
 FILED FOR PUBLIC RECORD SHALL CONTAIN THE ORIGINAL
 SIGNATURE OF THE DESIGN PROFESSIONAL OR THE PERSON
 TAKING RESPONSIBILITY FOR THE INFORMATION; PHOTO COPY
 SEAL AND SIGNATURES ARE NOT ACCEPTABLE. THE BUILDING
 OFFICIAL MAY ESTABLISH THROUGH DEPARTMENTAL POLICY,
 STANDARDS FOR PLANS AND SPECIFICATIONS, IN ORDER TO
 PROVIDE CONFORMITY TO ITS RECORD RETENTION PROGRAM.
 106.1.3*
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]
  