Date Text
2007-12-21 07:02:01 
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC.
 IF AN ARCHITECT OR ENGINEER, COMPLY WITH 481 AND 471
 FS, RESPECTIVELY.
 THE CONTRACTOR OF RECORD MAY BE THE DESIGN PROFESSIONAL
 IF EXEMPTIONS UNDER CHAPTER 471.003, FLORIDA STATUTES,
 IF EXEMPTIONS APPLY.
  
 2} 301.5 FBC EXISTING BUILDING CODE. THE DESIGN
 PROFESSIONAL OR OWNER MUST ELECT THE LEVEL OF
 ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF THE
 EXISTING BUILDING CODE. PLEASE DECLARE SAME ON THE
 PLAN.
  
 3} SHOW ACCESS TO THE UPSTAIRS APARTMENT SO
 REQUIREMENTS OF EGRESS ILLUMINATION PER 210.70 CAN BE
 REVIEWED,
  
 4} INDICATE COMPLIANCE WITH NFPA-72- 11.5.4 EXISTING
 APARTMENT BUILDINGS. 11.5.4.1 DETECTION. WHERE REQUIRED
 BY APPLICABLE LAWS, CODES, OR STANDARDS FOR THE
 SPECIFIED OCCUPANCY, APPROVED SINGLE- AND
 MULTIPLE-STATION SMOKE ALARMS SHALL BE INSTALLED AS
 FOLLOWS:
 (1) OUTSIDE OF EACH SEPARATE SLEEPING AREA, IN THE
 IMMEDIATE VICINITY OF THE SLEEPING ROOMS
 (2) ON EACH LEVEL OF THE DWELLING UNIT, INCLUDING
 BASEMENTS.
  
 OTHER COMMENTS MAY BE APPLICABLE UPON HAVING THE LEVEL
 OF ALTERATION DECLARED AS WAS ASKED FOR IN THE LAST
 REVIEW BY THE BUILDING REVIEWER.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  