2007-12-20 07:30:00BUILDING PLAN REVIEW
 PERMIT: 07070569
 ADD: 7101 S. DIXIE HWY
 CONT: JUAN RUBIO (OWNER)
 TEL: (561)547-8704
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 2ND
 ACTION: DENIED
 12-19-07
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2)SUBMIT AN EXISTING AND A PROPOSED FLOOR PLAN
 SHOWING CLEARLY WHERE THE PROPOSED WORK WILL TAKE
 PLACE.
  
 **NO RESPONSE NOT ADDRESSED**
 3) ALL PLANS SUBMITTED AFTER OCTOBER, 1, 2004 SHALL BE
 DESIGNED TO THE 2004 FLORIDA BUILDING CODE/WITH THE
 2006 REV. **NEW** THIS INFORMATION ALONG WITH THE SCOPE
 OF WORK SHALL BE INDICATED ON THE DRAWINGS. THE PERSON
 RESPONSIBLE FOR THE DESIGN SHALL DATE, PRINT AND SIGH
 HIS/HER NAME ON THE DRAWINGS.
  
 4)FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 **NO RESPONSE NOT ADDRESSED**
 5) 2004 FBC EXISTING
 301.5 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
  
 **NO RESPONSE NOT ADDRESSED**
 6)FBC.TABLE 803.3 MINIMUM INTERIOR FINISH
 CLASSIFICATION; PROVIDE INFORMATION BASED ON INTERIOR
 FINISH REQUIREMENTS BASED ON OCCUPANCY
  
 7)OK
  
 **NOTED HOWEVER, GLAZED OPENINGS (WINDOWS/DOORS)
 LOCATED WITHIN 30 FEET SHALL HAVE LARGE MISSILE IMPACT
 PROTECTION. FBC 1609.1.4(1). IS THERE ANY HURRACINE
 PROTECTION FOR THE WINDOWS?
 8)106.3.3* PRODUCT APPROVALS- 2004. THOSE PRODUCTS
 THAT ARE REGULATED BY DCA
 RULE 9B-72 SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. PROVIDE TWO SETS OF PRODUCT
 APPROVALS FOR THE WINDOWS. IF THE WINDOWS ARE
 NON-IMPACT, THEN PRODUCT APPROVALS WILL BE REQUIRED FOR
 THE IMPACT PROTECTION OF EACH WINDOW.
  
 NOTE: AS AN OWNER/BUILDER YOU CANNOT LEASE THE PORTION
 OF THE BUILDING WHICH IS BEING IMPROVED. FLORIDA
 STATUTES 489 PART 1.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726