| Date |
Text |
| 2007-07-23 07:41:05 | |
| | |
| | |
| | NONCOMPLIANT |
| | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE |
| | COMPLIANCE AND RESUBMIT FOR REVIEW. |
| | |
| | 1} } PER 110.9 AND 110.10: OBTAIN THE |
| | AVAILABLE FAULT CURRENT AT THE UTILITY |
| | AND CALCULATE THE SAME AT THE EQUIPMENT. |
| | INDICATE THE AIC RATING FOR THE |
| | EQUIPMENT IS EQUAL TO OR GREATER THAN |
| | THE AVAILABLE FAULT. |
| | |
| | 2} INDICATE HOW THE MAIN HOUSE IS BEING FED. THE PLAN |
| | SHOWS ONLY ONE PANEL LOCATION. PLEASE LOCATE ALL |
| | SERVICE EQUIPMENT ON THE PLAN, METER ENCLOSURE, |
| | DISCONNECTS AND PANELS, SO THAT COMPLIANCE WITH |
| | ARTICLES 225 AND 230 CAN BE REVIEWED. |
| | |
| | 3} BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE |
| | PER 210.11(C) (3), LOCATED PER 210.52(D), AND BE GFI |
| | PROTECTED PER 210.8(A) (1). INDICATE SAME ON THE PLAN. |
| | |
| | 4} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST |
| | PRINT AND SIGN THEIR NAME TO SAME, ALL SHEETS, PER |
| | 106.3.4.3.FBC. |
| | |
| | 5} R313.1.1 ALTERATIONS, REPAIRS AND ADDITIONS. WHEN |
| | INTERIOR ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A |
| | PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE |
| | ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL |
| | DWELLING UNIT SHALL BE PROVIDED WITH SMOKE ALARMS |
| | LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE ALARMS |
| | SHALL BE INTERCONNECTED AND HARD WIRED INDICATE |
| | LOCATIONS AND INTENT ON THE PLAN. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561/805-6718 |