2007-08-07 16:53:14*****DENIED*****
  
  
 1.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 3.THE REMOVAL AND/OR THE REPLACEMENT OF BUILDING
 MATERIALS & SUPPLIES SHALL NOT INTERFERE OR HINDER
 ACCESS TO OR EGRESS FROM THE 14TH FLOOR CORRIDOR OR ANY
 OTHER FLOOR IN THE BUILDING.
  
 4.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL
 BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR
 MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 5.IT IS STATED IN THE DEMOLITION PLAN THAT ALL WALL
 AND FLOOR FINISH ARE BE REMOVED IN THE BATHROOM.
 SPECIFY THE REPLACED INTERIOR FINISH MATERIAL FOR THE
 BATHROOM WALL IN TERMS OF CLASS A, CLASS B, OR CLASS
 C.
  
 6.IF THE SCOPE OF WORK HAS CAUSE FOR THE FIRE
 SPRINKLERS TO BE ALTERED OR REMODELED, A SEPARATE
 PERMIT AND PLAN WILL BE REQUIRED.
  
 7.PLEASE SHOW/DISPLAY THE UNIT SPACE'S SMOKE
 DETECTION DEVICES AS EITHER SMOKE DETECTORS OR SMOKE
 ALARMS.PLEASE BE ADVISED THAT SMOKE DETECTORS (SD)
 ARE TIED INTO THE BUILDING'S FIRE ALARM SYSTEM WHEREAS
 SMOKE ALARMS (SA) ALERT THE OCCUPANT(S) OF THE UNIT
 SPACE ONLY.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE PLANS EACH ITEM WAS
 ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW