| 2007-08-07 16:53:14 | *****DENIED***** |
| | |
| | |
| | 1.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE |
| | REFERENCED. |
| | |
| | 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. |
| | |
| | 3.THE REMOVAL AND/OR THE REPLACEMENT OF BUILDING |
| | MATERIALS & SUPPLIES SHALL NOT INTERFERE OR HINDER |
| | ACCESS TO OR EGRESS FROM THE 14TH FLOOR CORRIDOR OR ANY |
| | OTHER FLOOR IN THE BUILDING. |
| | |
| | 4.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL |
| | BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR |
| | MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION. |
| | |
| | 5.IT IS STATED IN THE DEMOLITION PLAN THAT ALL WALL |
| | AND FLOOR FINISH ARE BE REMOVED IN THE BATHROOM. |
| | SPECIFY THE REPLACED INTERIOR FINISH MATERIAL FOR THE |
| | BATHROOM WALL IN TERMS OF CLASS A, CLASS B, OR CLASS |
| | C. |
| | |
| | 6.IF THE SCOPE OF WORK HAS CAUSE FOR THE FIRE |
| | SPRINKLERS TO BE ALTERED OR REMODELED, A SEPARATE |
| | PERMIT AND PLAN WILL BE REQUIRED. |
| | |
| | 7.PLEASE SHOW/DISPLAY THE UNIT SPACE'S SMOKE |
| | DETECTION DEVICES AS EITHER SMOKE DETECTORS OR SMOKE |
| | ALARMS.PLEASE BE ADVISED THAT SMOKE DETECTORS (SD) |
| | ARE TIED INTO THE BUILDING'S FIRE ALARM SYSTEM WHEREAS |
| | SMOKE ALARMS (SA) ALERT THE OCCUPANT(S) OF THE UNIT |
| | SPACE ONLY. |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER INDICATING WHERE ON THE PLANS EACH ITEM WAS |
| | ADDRESSED. |
| | |
| | |
| | CAPT. MICHAEL A. WILLIAMS |
| | FIRE PLAN REVIEW |
| | 561-805-6722 |