| 2007-07-30 10:50:31 | |
| | |
| | |
| | NONCOMPLIANT |
| | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE |
| | COMPLIANCE AND RESUBMIT FOR REVIEW. |
| | |
| | 1} THE DESCRIPTION OF WORK ON THE APPLICATION INDICATES |
| | "UPGRADING" THE ELECTRICAL PANEL. IT IS NOT CLEAR IF |
| | THE INTENT IS TO INSTALL A LARGER AMPERAGE PANEL. |
| | INDICATE THE AMPERAGE ON THE PANELON THE PLAN. NOTE: |
| | IF INCREASING AMPERAGE, INDICATE THE FEEDER SIZE AND |
| | TYPE. |
| | |
| | 2} PER 210.11(C)(1), THERE MUST BE 2 SMALLAPPLIANCE |
| | CIRCUITS IN THE KITCHEN. THERE ARE TWO IN THE PANEL |
| | (5,7), BUT ONLY #5 APPEARS ON THE FLOOR PLAN CIRCUIT |
| | DESIGNATION. ALSO SEE 210.52(B)(1) REGARDING THE NOOK. |
| | |
| | |
| | 3} R313.1.1 ALTERATIONS, REPAIRS AND ADDITIONS. |
| | WHEN INTERIOR ALTERATIONS, REPAIRS OR ADDITIONS |
| | REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING |
| | ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE |
| | INDIVIDUAL DWELLING UNIT SHALL BE PROVIDED WITH SMOKE |
| | ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE |
| | ALARMS SHALL BE INTERCONNECTED AND HARD WIRED. PLEASE |
| | LOCATE THE ALARMS ON THE DRAWING FLOOR PLAN FOR CLARITY |
| | IN THE FIELD, OR NOTE SECTION 313 ON THE PLAN. |
| | |
| | 4} PER 2704.1, 2004 FBC, METAL FRAMING MEMBERS SHALL BE |
| | BONDED TO THE EQUIPMENT GROUNDING CONDUCTOR FOR THE |
| | CIRCUIT THAT MAY ENERGIZE THE FRAMING. PLEASE NOTE ON |
| | PLAN. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |