Plan Review Notes
Plan Review Notes For Permit 07070532
Permit Number 07070532
Review Stop E
Sequence Number 1
Notes
Date Text
2007-07-30 10:50:31 
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} THE DESCRIPTION OF WORK ON THE APPLICATION INDICATES
 "UPGRADING" THE ELECTRICAL PANEL. IT IS NOT CLEAR IF
 THE INTENT IS TO INSTALL A LARGER AMPERAGE PANEL.
 INDICATE THE AMPERAGE ON THE PANELON THE PLAN. NOTE:
 IF INCREASING AMPERAGE, INDICATE THE FEEDER SIZE AND
 TYPE.
  
 2} PER 210.11(C)(1), THERE MUST BE 2 SMALLAPPLIANCE
 CIRCUITS IN THE KITCHEN. THERE ARE TWO IN THE PANEL
 (5,7), BUT ONLY #5 APPEARS ON THE FLOOR PLAN CIRCUIT
 DESIGNATION. ALSO SEE 210.52(B)(1) REGARDING THE NOOK.
  
  
 3} R313.1.1 ALTERATIONS, REPAIRS AND ADDITIONS.
 WHEN INTERIOR ALTERATIONS, REPAIRS OR ADDITIONS
 REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING
 ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE
 INDIVIDUAL DWELLING UNIT SHALL BE PROVIDED WITH SMOKE
 ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE
 ALARMS SHALL BE INTERCONNECTED AND HARD WIRED. PLEASE
 LOCATE THE ALARMS ON THE DRAWING FLOOR PLAN FOR CLARITY
 IN THE FIELD, OR NOTE SECTION 313 ON THE PLAN.
  
 4} PER 2704.1, 2004 FBC, METAL FRAMING MEMBERS SHALL BE
 BONDED TO THE EQUIPMENT GROUNDING CONDUCTOR FOR THE
 CIRCUIT THAT MAY ENERGIZE THE FRAMING. PLEASE NOTE ON
 PLAN.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER