| 2007-08-08 18:29:29 | BUILDING PLAN REVIEW | | | PERMIT: 07070532 | | | ADD: 1801 S. FLAGLER DR #1409 | | | CONT: FINE DETAILS INC. | | | TEL: (561)###-#### | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2006 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW: 1ST | | | ACTION: DENIED | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR | | | YOUR ANTICIPATED COOPERATION. | | | | | | 2)FBC 2406.3 (5)SAFETY GLAZING SHALL BE INSTALLED | | | IN THE SHOWER AREA. PROVDE PRODUCT APPROVALS FOR THE | | | GLASS BLOCK. SHOW IN DETAIL HOW THE GLASS BLOCK WALL | | | WILL BE HELD IN PLACE AND WHAT MATERIALS WILL BE USED | | | TO RESTRAIN THE WALL FROM OVER-TURNING. | | | | | | 3)SHOW ON THE DRAWINGS THE DOOR FOR THE SHOWER, OR | | | STATE IF ANOTHER OPTION WILL BE USED. IF THE SHOWER | | | DOOR IS GLASS, IT SHALL BE SAFETY GLAZING ALSO. | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | (561)805-6726 | | | [email protected] | | | |
|