| 2007-08-10 18:31:19 | NEW POOL FIRST BUILDING REVIEW CHECKLIST: |
| | REVIEW DONE UNDER CHAPTER 41 OF 2004 FLORIDA |
| | RESIDENTIAL CODE AND FBC 2004. |
| | |
| | 1- DRAWING ON SHEET 1 OF 2 IS NOT DRAWN TO SCALE. NEED |
| | TO DRAW TO TRUE SCALE TO VERIFY COMPLIANCE WITH |
| | SETBACKS AND DISTANCE FROM POOL TO BUILDING. SEC. |
| | 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| | |
| | 2- PROVIDE INFORMATION IF THERE ARE ANY WINDOWS ON WALL |
| | ADJACENT TO THE POOL IN THE EXISTING GARAGE AREA TO |
| | VERIFY COMPLIANCE WITH SAFETY GLAZING REQUIREMENTS OF |
| | SEC. R308.4(9). |
| | |
| | 3-A) SPECIFY ALL DIMENSIONS TO VERIFY COMPLIANCE WITH |
| | SEC. R4101.18REGARDING STEPS OR BENCHES. |
| | |
| | B) NEED TO PROVIDE STEPS OR BENCH AT DEEP AREA AS |
| | REQUIRED BY THE ABOVE SECTION ON ITEM 3(A). |
| | |
| | 4- NOTES REGARDING SWIMMING POOL BARRIER REQUIREMENTS |
| | NEED TO BE REVISED. |
| | A) NOTE #1 IS TO IMPEDE ACCESS FROM THE HOUSE TO THE |
| | POOL, NOT FROM THE POOL TO THE HOUSE. REVISE AS |
| | REQUIRED. SEE SEC. R4101.17 OF 2004 FLORIDA RESIDENTIAL |
| | CODE. |
| | |
| | B) THE BARRIER REQUIREMENTS APPLIES TO THE ACCESS |
| | FROM THE HOUSE TO THE POOLAND FROM THE ACCESS FROM |
| | OUTSIDE TO THE POOL. CLEARLY SPECIFY HOW COMPLYING WITH |
| | BOTH AS REQUIRED BY SEC. 4101.17 OF 2004 FLORIDA |
| | RESIDENTIAL CODE. |
| | |
| | 5- THIS IS A RESIDENTIAL POOL, THEREFORE CODE TO BE |
| | REFERENCED IS 2004 FLORIDA RESIDENTIALCODE CHAPTER |
| | 41. REVISE ALL NOTES AS REQUIRED. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |