| 2008-03-18 15:16:22 | ** DENIED 4TH REVIEW ** |
| | |
| | ** PLEASE SEE COMMENT IS THE SAME FROM PREVIOUS REVIEW |
| | WHICH ARE STILL IN NEED OF ADDRESSING. |
| | |
| | |
| | 1) NOTE: PLEASE SEE THE LIGHTING PERFORMANCE |
| | CALCULATIONS ON PLANS DO NOT COORDINATE WITH THE |
| | ELECTRICAL LIGHTING SHOWN. |
| | PLEASE SEE SOME OF THESE APPEAR TO BE MISPRINTS HOWEVER |
| | SOME AREAS ARE NOT CLEAR AS THEY DO NOT CONTAIN LABELS, |
| | OR IDENTIFICATIONS OF ANY KIND AND LIGHTING BEING |
| | FIGURED INTO SOME OF THESE AREAS ARE ONLY BEING |
| | "ASSUMED". |
| | PLEASE SEE SOME OF AREA DESIGNATIONS ARE NOT LISTED ON |
| | THE CALCULATIONS AND SOME OF THE ITEMS LISTED ON THE |
| | CALCULATIONS ARE NOT ON PLANS. |
| | PLEASE SEE FOR EXAMPLE: OFFICE 17 IS SHOWN TWICE ON |
| | PLANS, OFFICE AREA 18 ON PLANS NOT LISTED ON |
| | CALCULATIONS, CONFERENCE ROOM #15 ON PLANS, NOT LISTED |
| | ON CALCULATIONS ETC |
| | PLEASE SEE FOR EXAMPLE: OFFICE AREA #21, SOME OTHER |
| | OFFICE AREAS LIKE #24 INCLUDED THE COPY ROOMS EVEN |
| | THOUGH NONE OF THESE WERE LABELED IN CALCULATIONS THIS |
| | WAS FIGURED BY THIS OFFICE. HOWEVER PLEASE SEE #21 AS |
| | THE COPY ROOM IN THIS AREA WAS NOT FIGURED IN THE AREA |
| | CALCULATIONS. |
| | PLEASE SEE FOR EXAMPLE: THERE IS A MARKETING CLOSET #32 |
| | SHOWN ON CALCULATIONS HOWEVER WHERE IS THIS ON PLANS? |
| | |
| | PLEASE GO OVER ALL LIGHTING, ROOM/AREA DESIGNATIONS |
| | PLEASE CORRELATE AND COORDINATE ALLOWANCES. 13-415.2, |
| | 13-415.2.ABC.1.1, .1.2, 13-415.2.B |
| | |
| | ** PLEASE KNOW ONE COPY OF E-1 WILL BE RETAINED BY THIS |
| | OFFICE. |
| | |
| | 2) NOTE: ** ATTENTION CONTRACTOR**/ PHOENIX REALTY. |
| | WHEN PRINTING ON-LINE FORM, AS INSTRUCTED AT THE TOP OF |
| | WEB- PAGE; PLEASE CLICK ON THE "SUBMIT" BUTTON IN ORDER |
| | TO PRINT THE CORRECT RE-SUBMISSION FORM. THE *PRINT |
| | SCREEN* SHEET USED WHEN RESUBMITTED WAS NOT CORRECT AND |
| | SHOULD NOT HAVE BEEN USED OR SUBMITTED. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |