Date Text
2008-03-18 15:16:22** DENIED 4TH REVIEW **
  
 ** PLEASE SEE COMMENT IS THE SAME FROM PREVIOUS REVIEW
 WHICH ARE STILL IN NEED OF ADDRESSING.
  
  
 1) NOTE: PLEASE SEE THE LIGHTING PERFORMANCE
 CALCULATIONS ON PLANS DO NOT COORDINATE WITH THE
 ELECTRICAL LIGHTING SHOWN.
 PLEASE SEE SOME OF THESE APPEAR TO BE MISPRINTS HOWEVER
 SOME AREAS ARE NOT CLEAR AS THEY DO NOT CONTAIN LABELS,
 OR IDENTIFICATIONS OF ANY KIND AND LIGHTING BEING
 FIGURED INTO SOME OF THESE AREAS ARE ONLY BEING
 "ASSUMED".
 PLEASE SEE SOME OF AREA DESIGNATIONS ARE NOT LISTED ON
 THE CALCULATIONS AND SOME OF THE ITEMS LISTED ON THE
 CALCULATIONS ARE NOT ON PLANS.
 PLEASE SEE FOR EXAMPLE: OFFICE 17 IS SHOWN TWICE ON
 PLANS, OFFICE AREA 18 ON PLANS NOT LISTED ON
 CALCULATIONS, CONFERENCE ROOM #15 ON PLANS, NOT LISTED
 ON CALCULATIONS ETC
 PLEASE SEE FOR EXAMPLE: OFFICE AREA #21, SOME OTHER
 OFFICE AREAS LIKE #24 INCLUDED THE COPY ROOMS EVEN
 THOUGH NONE OF THESE WERE LABELED IN CALCULATIONS THIS
 WAS FIGURED BY THIS OFFICE. HOWEVER PLEASE SEE #21 AS
 THE COPY ROOM IN THIS AREA WAS NOT FIGURED IN THE AREA
 CALCULATIONS.
 PLEASE SEE FOR EXAMPLE: THERE IS A MARKETING CLOSET #32
 SHOWN ON CALCULATIONS HOWEVER WHERE IS THIS ON PLANS?
  
 PLEASE GO OVER ALL LIGHTING, ROOM/AREA DESIGNATIONS
 PLEASE CORRELATE AND COORDINATE ALLOWANCES. 13-415.2,
 13-415.2.ABC.1.1, .1.2, 13-415.2.B
  
 ** PLEASE KNOW ONE COPY OF E-1 WILL BE RETAINED BY THIS
 OFFICE.
  
 2) NOTE: ** ATTENTION CONTRACTOR**/ PHOENIX REALTY.
 WHEN PRINTING ON-LINE FORM, AS INSTRUCTED AT THE TOP OF
 WEB- PAGE; PLEASE CLICK ON THE "SUBMIT" BUTTON IN ORDER
 TO PRINT THE CORRECT RE-SUBMISSION FORM. THE *PRINT
 SCREEN* SHEET USED WHEN RESUBMITTED WAS NOT CORRECT AND
 SHOULD NOT HAVE BEEN USED OR SUBMITTED.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved