2008-02-14 11:10:46REVIEW #: 3RD
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1. OK. THIS COMMENT NO LONGER APPLIES AS THE BASE
 BUILDING HAS BEEN COMPLETED.
  
 2. OK FOR MECHANICAL PORTIONS OF FBC CHAPTER 13 ONLY.
  
 3 THROUGH 10: OK
  
 11. BY WHAT MEANS ARE THE MOTORIZED DAMPERS ON THE
 OUTSIDE AIR INTAKES CONTROLLED? WILL THEY CLOSE
 WHENEVER THE AHUS SHUT DOWN OR WILL THEY CLOSE WHEN THE
 BUILDING A/C IS IN UNOCCUPIED MODE? THE LATTER IS WHAT
 IS REQUIRED BY FBC 13-409.1.ABC.3.4.
  
 12. OK
  
 13. AS STATED IN PREVIOUS REVIEW COMMENT #13, WHEN
 COMBINED SYSTEMS EXCEEDING 2000 CFM SHARE A COMMON
 PLENUM, SMOKE DETECTORS SHALL BE INSTALLED ON THE
 SUPPLY AND RETURN SYSTEMS IN ACCORDANCE WITH FBC, M
 606.2.2. AC-1, 2, 4, 6 AND 8 SHOULD ALL HAVE SMOKE
 DETECTORS ON THE SUPPLY AND RETURN SIDES IN ACCORDANCE
 WITH THIS SECTION. PLEASE CORRECT AND RESUBMIT.
  