| Plan Review Notes For Permit 07070482 |
| Permit Number |
07070482 |
|
| Review Stop |
FIRE |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2008-02-27 14:06:49 | ***DENIED*** | | | | | | PLEASE NOTE THAT MOST OF THE COMMENTS HAVE BEEN | | | ADDRESSED ON THE PLANS. THE FOLLOWING COMMENTS TAKEN | | | FROM THE LAST REVIEW REQUIRE A WRITTEN RESPONSE. A | | | RESPONSE LETTER ADDRESSING THESE COMMENTS WOULD HELP | | | EXPEDITE THIS PLAN REVIEW PROCESS: | | | | | | 06. IN THE EVENT OF A FIRE, STAIRWELLS INSTEAD OF THE | | | ELEVATORS WILL BE USED. PLEASE EXPLAIN RATIONALE FOR | | | GOING THROUGH THE CONFERENCE ROOM OR GOING THROUGH THE | | | BREAK ROOM TO ACCESS THOSE FIRE-RATED STAIRWELLS. | | | PROVIDE DATA/CRITERIA AS PER NFPA 101, CHAPTER-7 THAT | | | ALLOWS THIS ARRANGEMENT. | | | | | | 10. HOW DOES A PERSON(S) GET IN OR OUT OF THE MODULAR | | | OFFICES? PLEASE ACKNOWLEDGE | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|