| 2008-02-01 17:49:17 | ** DENIED 3RD REVIEW ** |
| | |
| | 1) NOTE: PLEASE SEE NOTES FROM PREVIOUS REVIEW WITH |
| | RESPECT TO LIGHTING PERFORMANCE CALCULATIONS. |
| | RESPONSE LETTERS MENTIONS NO ENERGY CALCULATIONS WERE |
| | TO BE SUBMITTED. SHELL PERMIT HAD THESE ITEMS AS |
| | ASSUMPTIONS, SHELL PERMIT IS ALSO NOW HAS A CERTIFICATE |
| | OF OCCUPANCY SINCE LAST REVIEW. |
| | PLEASE KNOW THE LIGHTING PERFORMANCE CALCULATIONS AS |
| | NOTED ON SHEET E-1 ARE NOT ENOUGH FOR REVIEW. |
| | PLANS MENTIONS METHOD *B* BEING USED, HOWEVER COULD NOT |
| | LOCATE SPACE BY SPACE CALCULATIONS. THERE ARE ALSO |
| | OTHER SPACES BESIDE THE ONES LISTED ON PLANS WHICH DO |
| | FALL UNDER OTHER AREAS IN TABLE 13-415.2.B. |
| | LEVELS AS SHOWN ON PLANS NEED TO COMPLY WITH TABLE *B* |
| | AS NOTED. FOR EXAMPLE: PLEASE SEE HALLWAYS WHICH PLANS |
| | INDICATES 1.0 YET THE FBC TABLE *B* SHOWS .05 (MAX). |
| | PLEASE SEE AS STATED ON PREVIOUS REVIEW THE LEVELS |
| | WHICH NEED TO BE SHOWN AND FIGURED FOR TRACK LIGHTING |
| | PER 13-415.2.ABC.1.2 |
| | PLEASE CALL TO GO OVER HOW COMPLIANCE NEEDS TO BE |
| | SHOWN. |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |