2008-02-01 17:49:17** DENIED 3RD REVIEW **
  
 1) NOTE: PLEASE SEE NOTES FROM PREVIOUS REVIEW WITH
 RESPECT TO LIGHTING PERFORMANCE CALCULATIONS.
 RESPONSE LETTERS MENTIONS NO ENERGY CALCULATIONS WERE
 TO BE SUBMITTED. SHELL PERMIT HAD THESE ITEMS AS
 ASSUMPTIONS, SHELL PERMIT IS ALSO NOW HAS A CERTIFICATE
 OF OCCUPANCY SINCE LAST REVIEW.
 PLEASE KNOW THE LIGHTING PERFORMANCE CALCULATIONS AS
 NOTED ON SHEET E-1 ARE NOT ENOUGH FOR REVIEW.
 PLANS MENTIONS METHOD *B* BEING USED, HOWEVER COULD NOT
 LOCATE SPACE BY SPACE CALCULATIONS. THERE ARE ALSO
 OTHER SPACES BESIDE THE ONES LISTED ON PLANS WHICH DO
 FALL UNDER OTHER AREAS IN TABLE 13-415.2.B.
 LEVELS AS SHOWN ON PLANS NEED TO COMPLY WITH TABLE *B*
 AS NOTED. FOR EXAMPLE: PLEASE SEE HALLWAYS WHICH PLANS
 INDICATES 1.0 YET THE FBC TABLE *B* SHOWS .05 (MAX).
 PLEASE SEE AS STATED ON PREVIOUS REVIEW THE LEVELS
 WHICH NEED TO BE SHOWN AND FIGURED FOR TRACK LIGHTING
 PER 13-415.2.ABC.1.2
 PLEASE CALL TO GO OVER HOW COMPLIANCE NEEDS TO BE
 SHOWN.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  