Plan Review Notes
Plan Review Notes For Permit 07070482
Permit Number 07070482
Review Stop M
Sequence Number 2
Notes
Date Text
2007-11-29 14:33:58REVIEW #: 2ND
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 AMENDMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 NOTE: MECHANICAL RESPONSES TO REVIEW COMMENTS WERE NOT
 SUBMITTED WITH THE PERMIT PACKAGE. MULTIPLE ATTEMPTS
 WERE MADE TO CONTACT DESIGNER AND OBTAIN COMMENTS
 BEFORE THEY WERE PROVIDED. AFTER WAITING FROM 11/17/07
 TO 11/28/07 THE REVIEW WAS STARTED WITHOUT THE
 RESPONSES. THE RESPONSES WERE RECEIVED ON 11/29/07
 AFTER THE REVIEW WAS UP TO COMMENT #11.
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1. THIS COMMENT HAS NOT BEEN ADDRESSED. THIS PERMIT
 WILL NOT BE ISSUED PRIOR TO A PASSED FINAL INSPECTION
 OF THE BASE BUILDING WITHOUT A SHOP DRAWING REVIEW OF
 THESE PLANS BY THE BASE BUILDING DESIGNERS OF RECORD.
 IT IS NOTED THAT THE BASE BUILDING IS CLOSE TO FINAL AT
 THIS TIME.
  
 2. METHOD A COMPLIANCE FOR A TENANT BUILD-OUT IN AN
 UNFINISHED SHELL BUILDING IS NOT THE CORRECT METHOD OF
 COMPLIANCE IN ACCORDANCE WITH FBC 13-101.1.6. ALSO, IF
 THE BASE BUILDING IS COMPLETE PRIOR TO RESUBMITTAL,
 COMPLIANCE SHALL BE DETERMINED AND DEMONSTRATED IN
 ACCORDANCE WITH FBC 13-400.0.C.4. METHOD A COMPLIANCE
 IS FOR A WHOLE BUILDING AND THIS IS NOT A WHOLE
 BUILDING PERMIT.
  
 3. EQUIPMENT SCHEDULE HAS BEEN CORRECTED TO CORRESPOND
 WITH OUTSIDE AIR CALCULATIONS. PLEASE SEE COMMENT #4
 BELOW FOR ADDITIONAL INFORMATION.
  
 4. FBC, M TABLE 403.3 DOES NOT MAKE ANY PROVISIONS FOR
 REDUCING THE RATE OF OUTSIDE AIR BY 50% BASED ON THE
 DURATION OF OCCUPANCY. NOTE THAT THE DESIGNER HAS THE
 OPTION OF DESIGNING THE MECHANICAL VENTILATION SYSTEM
 TO ASHRAE 62.1-2004 IN LIEU OF COMPLIANCE WITH SECTION
 403.1 THROUGH SECTION 403.3. HOWEVER, THERE ARE NO
 PROVISIONS FOR USING PARTS OF SECTION 403 AND PARTS OF
 ASHRAE 62.1. THE DESIGNER SHALL DECLARE WHICH METHOD IS
 TO BE USED AND DESIGN BY THAT METHOD EXCLUSIVELY IN
 ACCORDANCE WITH FBC, M 403.4. NOTE: IF THE DESIGNER
 CHOOSES TO DESIGN PER ASHRAE 62.1, THE MECHANICAL
 VENTILATION SYSTEM WILL BE REVIEWED FOR COMPLIANCE WITH
 ALL APPLICABLE SECTIONS OF THAT STANDARD, NOT JUST
 OUTSIDE AIR RATES.
  
 5. OK
  
 6. OK
  
 7. OK
  
 8. THE AIR BALANCE SCHEDULE SHOWS A POSITIVE PRESSURE
 OF 1410 CFM. WHILE FBC 13-409.1.ABC.2 REQUIRES THE
 BUILDING TO BE PRESSURIZED, COMPLIANCE WITH FBC, M
 403.1 SHALL ALSO BE SHOWN. THE AMOUNT OF SUPPLY AIR
 SHALL BE APPROXIMATELY EQUAL TO THE AMOUNT OF RETURN
 AND EXHAUST AIR AS REQUIRED BY FBC, M 403.1. SUPPLY AIR
 IS SHOWN AT 12,000 CFM AND RETURN PLUS EXHAUST IS SHOWN
 AT 10,590 CFM. IN ACCORDANCE WITH FBC 201.3, WORDS NOT
 DEFINED IN THE FBC SHALL HAVE THE MEANINGS IN WEBSTER?S
 THIRD NEW INTERNATIONAL DICTIONARY OF THE ENGLISH
 LANGUAGE, UNABRIDGED. APPROXIMATE IS DEFINED AS "NEARLY
 CORRECT OR EXACT." THE IMPLEMENTATION OF THESE TWO CODE
 SECTIONS TOGETHER WOULD REQUIRE THESE NUMBERS TO BE
 NEARLY EQUAL, WITH A SLIGHT VARIATION TO THE POSITIVE
 SIDE AND THE OUTSIDE AIR BEING APPROXIMATELY EQUAL TO
 THE AMOUNT OF EXHAUST. SHOW COMPLIANCE WITH THESE
 SECTIONS.
  
 9. OK. MANUAL BALANCING DAMPERS ARE SHOWN ON PLAN. THIS
 IS NOT THE SAME AS SHUTOFF DAMPER CONTROLS AS STATED IN
 COMMENT #11 BELOW.
  
 10. SEE COMMENT #8 ABOVE.
  
 11. THIS ISSUE WAS NOT ADDRESSED ON PLANS. DESIGNER'S
 RESPONSE STATES "NO MOTORIZED DAMPERS USED." IF NO
 MOTORIZED DAMPERS HAVE BEEN USED, THEN BY WHAT MEANS
 HAS COMPLIANCE WITH THIS SECTION BEEN DEMONSTRATED?
 MANUAL DAMPERS DO NOT MEET THIS REQUIREMENT. SHOW
 COMPLIANCE WITH FBC 13-409.1.ABC.3.4.
  
 12. THE EXAMPLE GIVEN IN PREVIOUS COMMENT WAS THE
 CONFERENCE ROOM. PLANS NOW SHOW 1200 CFM SUPPLY WITH
 940 CFM RETURN. THIS WOULD ALLOW FOR ONLY 260 CFM
 OUTSIDE AIR. THE OUTSIDE AIR SCHEDULE SHOWS 500 CFM
 OUTSIDE AIR IS REQUIRED IN THIS ROOM IF THE SYSTEM IS
 DESIGNED TO ASHRAE 62.1-2004 (SEE COMMENT #4 ABOVE).
 SHOW AN AIR BALANCE IN ALL HIGH-OCCUPANCY AREAS WHICH
 WILL ALLOW FOR COMPLIANCE WITH OUTSIDE AIR
 REQUIREMENTS.
  
 13. BASED ON THE A/C SYMBOL LEGEND ON PG M1, DUCT
 MOUNTED SMOKE DETECTORS ARE NOT SHOWN ON PLANS. ALSO,
 ELECTRICAL PLANS ONLY SHOW PROVISIONS FOR TWO DUCT
 SMOKE DETECTORS ON AC-1 AND AC-6. SEE PG E2 FLOOR PLAN
 AND E4 FIRE ALARM RISER. SHOW COMPLIANCE WITH FBC, M
 606.2.1 AND 606.4.1. COORDINATE MECHANICAL AND
 ELECTRICAL PLANS TO SHOW COMPLIANCE WITH THESE
 SECTIONS.
  
 14. OK
  
 15. RESPONSE TO THIS COMMENT PROVIDED BY ARCHITECT.
 NOTE ON TITLE PAGE STATES THAT STANDS ON ROOF WERE
 INSTALLED AS PART OF BASE BUILDING PERMIT AND HAVE
 MIAMI-DADE NOA. THIS IS ACCEPTABLE. HOWEVER, THE MEANS
 BY WHICH THE CONDENSERS ATTACH TO THE STAND IS PART OF
 THE NOA AND THEREFORE SHALL BE A PART OF THIS PERMIT TO
 GOVERN THE INSTALLATION OF THE CONDENSING UNITS FOR
 THIS PERMIT. PLEASE PROVIDE THE NOA FOR THE PREVIOUSLY
 INSTALLED STANDS HEN RESUBMITTING PLANS. OPTION:
 PROVIDE NOA # AND THE CORRESPONDING ATTACHMENT DETAIL
 ON PLANS.
  
 16. DESIGNER'S RESPONSE: "THIS DETAIL FITS MOST AC
 UNITS." MOST AC UNITS HAVE NOT BEEN SPECIFIED FOR THIS
 PROJECT. ONLY ONE BRAND HAS BEEN SPECIFIED. IN FACT THE
 CARRIER MODEL FA4C AIR HANDLER INSTALLATION
 INSTRUCTIONS DO NOT CORRESPOND WITH THE DETAIL AS SHOWN
 ON PLANS. SEE PAGE FROM INSTALLATION INSTRUCTIONS
 ATTACHED TO THESE COMMENTS. PROVIDE DETAIL WHICH
 CORRESPONDS TO THE ONE IN THE INSTRUCTIONS OR REMOVE
 DETAIL FROM PLANS. A NOTE INSTRUCTING TRAP TO BE IN
 ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS WILL BE
 SUFFICIENT TO DEMONSTRATE CODE COMPLIANCE IN ACCORDANCE
 WITH FBC, M 307.2.4.
  
 17. PLEASE SEE COMMENT #2 ABOVE REGARDING ENERGY CODE
 COMPLIANCE.
  
 NOTE: THE DESIGNER'S COMMENTS WERE NUMBERED INCORRECTLY
 AS COMMENT #1 WAS SKIPPED. THEREFORE, THESE COMMENTS
 WILL NOT CORRESPOND WITH DESIGNER'S RESPONSE. SEE FIRST
 ROUND REVIEW COMMENTS FOR CORRECT NUMBERING SEQUENCE.
  
 NOTE: DUE TO THE AMOUNT OF INFORMATION WHICH IS STILL
 OUTSTANDING, ADDITIONAL REVIEW COMMENTS ARE POSSIBLE
 BASED ON THE INFORMATION PROVIDED WITH NEXT
 RESUBMITTAL.
  