| Date |
Text |
| 2007-12-11 15:44:08 | *****DENIED***** |
| | |
| | THE FOLLOWING COMMENTS FROM THE PREVIOUS FIRE PLAN |
| | REVIEW STILL NEED TO BE ADDRESSED: |
| | |
| | 01.THE LOCATION OF THE PROJECT AS INDICATED ON THE |
| | LOCATION MAP (COVER SHEET) IS INACCURATE.PLEASE BE |
| | ADVISED THAT THE PROJECT SITE LOCATION IS MUCH FARTHER |
| | WEST OF WHAT IS SHOWN |
| | |
| | 02.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.ADD |
| | COMMENT TOA 110.1 |
| | |
| | 04.IT APPEARS THAT THIS BUILDOUT WILL COMPRISE OF THE |
| | ENTIRE SECOND FLOOR.IF A SUITE NUMBER IS ASSIGNED TO |
| | THIS SITE,THE SUITE NEMBER SHALL BE INCLUDED IN THE |
| | ADDRESS LOCATED IN THE TITLE BLOCK OF EACH SUBMITTED |
| | PLAN SHEET.NO SUITE NUMBER SHOWN ONA110.1, A125.1, |
| | A150.1, A150.2, A150.4, A210.1, A400.2, A500.1, M1 THRU |
| | M7, E1 THRU E4, AND P1 THRU P3. |
| | |
| | 05.COULD NOT LOCATE SHEET A135.1 AS INDICATED IN THE |
| | SHEET INDEX OF THE COVER SHEET.PLAN SHEET NOT |
| | INCLUDED |
| | |
| | 06.IN THE EVENT OF A FIRE, STAIRWELLS INSTEAD OF THE |
| | ELEVATORS WILL BE USED.PLEASE EXPLAIN RATIONALE FOR |
| | GOING THROUGH THE CONFERENCE ROOM OR GOING THROUGH THE |
| | BREAK ROOM TO ACCESS THOSE FIRE-RATED STAIRWELLS. |
| | PROVIDE DATA/CRITERA AS PER NFPA 101 - CHAPTER 7 THAT |
| | ALLOWS THIS ARRANGEMENT |
| | |
| | 10.HOW DOES A PERSON(S) GET IN OR OUT OF THE MODULAR |
| | OFFICES?PLEASE ACKNOWLEDGE |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED |
| | |
| | |