| | ** DENIED 2ND REVIEW ** |
| | |
| | ** PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEW ARE STILL |
| | IN NEED OF ADDRESSING ALONG WITH SOME NEW COMMENTS DUE |
| | TO SOME CHANGES ON PLANS AND/OR DOCUMENTS AS |
| | SUBMITTED. |
| | SOME OF THESE COMMENTS COULD NOT HAVE BEEN MADE ON |
| | PREVIOUS REVIEWS AS THEY WERE NOT SUBMITTED. |
| | |
| | 1) NOTE: PLEASE SEE FROM PREVIOUS REVIEW STILL NEED TO |
| | SPECIFY MAXIMUM TIMES ON ALL LIGHTING CONTROL DEVICES. |
| | 13-415.1.ABC.1.1, .1.2. |
| | |
| | 2) NOTE: PLEASE KNOW IF ANY MODULAR FURNITURE HAS |
| | PERMANENTLY INSTALLED TASK LIGHTING, CONTROLS ARE |
| | REQUIRED PER 13-415.1.ABC .1.3. |
| | |
| | 3) NOTE: PLEASE SEE THE ENERGY CALCULATIONS AS |
| | SUBMITTED ARE METHOD *A* FOR WHOLE BUILDING. HOW IS |
| | THIS POSSIBLE WHEN THIS IS NOT A WHOLE BUILDING? PLEASE |
| | KNOW FOR ELECTRICAL AS THIS BUILDING IS ALREADY AIR |
| | CONDITIONED AND ASSUMPTIONS WERE DONE UNDER BASE |
| | BUILDING FOR SHELL, ONLY LIGHTING PERFORMANCE |
| | CALCULATIONS ARE NEEDED PER 13-415.2. |
| | PLEASE SEE EVEN AS THE METHOD *A* WAS SUBMITTED THE |
| | INFORMATION ON THE INPUT DATA REPORTS IS NOT CORRECT |
| | AND DOES NOT CORRELATE WITH THE AMOUNT OF FIXTURES, THE |
| | WATTAGE OF FIXTURES ETC AS REQUIRED TO BE ON THE INPUT |
| | DATA REPORT. FOR EXAMPLE: PLEASE SEE THE IDR, WHICH |
| | ONLY INDICATES *ONE* LIGHT FIXTURE BEING INSTALLED. |
| | THIS IS NOT POSSIBLE WHEN THERE ARE OVER A HUNDRED ON |
| | PLANS. |
| | ** PLEASE BE SURE TO SEE 13-415.2.ABC .1.2 FOR TRACK |
| | LIGHTING. |
| | ** PLEASE KNOW AS THIS IS NOT COMPLETE AT THIS TIME, A |
| | REVIEW OF THESE CAN NOT BE DONE. |
| | ** PLEASE BE SURE TO SEE COMMENTS FROM MECHANICAL OR |
| | OTHER TRADES WHICH WILL AFFECT THIS COMMENT ALSO. |
| | |
| | 4) NOTE: PLEASE SUBMIT LOAD CALCULATIONS PER NEC 220. |
| | PLEASE INDICATE ALL CONTINUOUS LOADS AT 125%. PLEASE |
| | SEE TRACK LIGHTING NEEDS TO BE SHOWN PER 220.43. |
| | 220.12, 220.14, 220.42, 220.43, 215.3, 230.42 ETC. FBC |
| | 106.3.5.1.2, 106.1.2 |
| | |
| | 5) NOTE: PLEASE SEEPREVIOUS COMMENT WITH RESPECT TO |
| | CODES ON PLANS. THIS IS REQUIRED ON ELECTRICAL PLANS AS |
| | STATED. |
| | PLEASE SEE THE FOLLOWING IS TO BE ON ELECTRICAL PLANS |
| | FOR THESE SETS OF RECORD PLANS. |
| | |
| | 2004 FBC W/ 2006 REVISIONS. |
| | 2005 NFPA-70 |
| | 2003 NFPA-101 |
| | 2002 NFPA-72 |
| | |
| | 6) NOTE: PLEASE KNOW THE ADDRESS FOR SUITE/UNIT NUMBER |
| | IS STILL NEEDED AND INFORMATION WAS FORWARDED TO THE |
| | ADDRESSING REVIEWER. |
| | PLEASE KNOW ONCE THE SUITE/UNIT NUMBER IS DETERMINED, |
| | PLEASE INCLUDE ON TITLE BLOCKS FOR ALL SHEETS. |
| | FBC 106.5, 106.1.2, FAC 61G15-23.002 |
| | |
| | 7) NOTE: PLEASE DO NOT ATTAH DOCUMENTS SUCH AS ENERGY |
| | CALCULATIONS, RESPONSES ETC DOWN THE LEFT HAND SIDE OF |
| | PLANS. |
| | |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |