| Date |
Text |
| 2007-09-01 18:07:05 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1. SHT 210.1 DETAILS 4, 10 & 15. ALL SINKS SHALL BE |
| | ACCESSIBLE. SHOW COMPLIANCE WITH THE FOLLOWING: |
| | A. 11-4.24.2 HEIGHT |
| | B. 11-4.24.3 KNEE CLEARANCE |
| | C. 11-4.24.4 SINK DEPTH |
| | D. 11-4.24.5 CLEAR FLOOR SPACE (FWD APPROACH REQUIRED |
| | - CABINET DOORS NOT APPROVED) |
| | E. 11-4.24.6 EXPOSED PIPES & SURFACES |
| | F. 11-4.24.7 FAUCETS |
| | |
| | 2. SHT P2 WATER RISER DIAGRAMS SHOW AIR CHAMBERS & SHT |
| | P3 GENERAL SPECIFICATIONS NOTE #$22 INDICATES AIR |
| | CHAMBERS. AIR CHAMBERS ARE NOT APPROVED. PLEASE DELETE |
| | FROM RISER DIAGRAMS AND DELETE NOTE #22. PDI-WH 201. |
| | |
| | 3. SHT P3 SUBMIT MANUF. SPECIFICATIONS SHEETS FOR THE |
| | ELECTRIC WATER HEATER. SHEETS SHALL SHOW THE LISTING & |
| | MANUF. INSTALLATION INSTRUCTIONS. SECTION 303.4. |
| | |
| | 4. ALL MEP SHEETS. ENGINEERS SHALL LEGIBLY INDICATE |
| | THEIR NAME, ADDRESS, AND LICENSE NUMBER, AS WELL AS, |
| | THE NAME, ADDRESS, AND CERTIFICATE OF AUTHORIZATION |
| | NUMBER OF THE ENGINEERING BUSINESS ON EACH SHEET. FAC |
| | 61G15.23.002(2) & FS 471.025. PLEASE INCLUDE THE CA |
| | NUMBER. ALSO THE ADDRESS DOES NOT REFLECT THE ADDRESS |
| | OF RECORD ON THE FLORIDA STATE DBPR WEBSITE. (SEE |
| | ATTACHED SHEET). PLEASE UPDATE THE ADDRESS ON EITHER |
| | THE DBPR WEBSITE OR THE TITLE BLOCKS PRIOR TO |
| | RESUBMITTING TO THE CITY WPB FOR REVIEW. |
| | |
| | 5. BASED ON THE DETERMINATION OF THE BUILDING OFFICIAL, |
| | APPLICATIONS FOR TENANT IMPROVEMENT PERMIT PRIOR TO |
| | C.O. OF THE BASE BUILDING REQUIRE THE DRAWINGS FOR |
| | TENANT BUILDOUT TO BE REVIEWED BY THE BASE BUILDING |
| | DESIGNERS OF RECORD. HAVE THE DESIGNERS OF RECORD |
| | REVIEW THE CONSTRUCTION DOCUMENTS PRIOR TO RESUBMITTING |
| | TO THE CITY FOR REVIEW AND, IF FOUND SUFFICIENT, AFFIX |
| | THEIR SHOP DRAWING REVIEW STAMP AND SIGNATURE ON SAID |
| | DOCUMENTATION. |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |