Plan Review Notes
Plan Review Notes For Permit 07070482
Permit Number 07070482
Review Stop M
Sequence Number 1
Notes
Date Text
2007-08-06 16:38:101ST REVIEW
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 UPDATES
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. BASED ON THE DETERMINATION OF THE BUILDING OFFICIAL,
 APPLICATIONS FOR TENANT IMPROVEMENT PERMITS PRIOR TO
 C.O. OF THE BASE BUILDING REQUIRE SHOP DRAWING REVIEW
 BY THE BASE BUILDING DESIGNER(S) OF RECORD. HAVE
 DESIGNER(S) OF RECORD REVIEW CONSTRUCTION DOCUMENTS
 PRIOR TO RESUBMITTAL AND, IF FOUND SUFFICIENT, AFFIX
 THEIR SHOP DRAWING REVIEW STAMP AND SIGNATURE ON SAID
 DOCUMENTATION.
  
 2. THE ENERGY CALCULATIONS FOR THE BASE BUILDING ARE
 BASED ON ASSUMPTIONS FOR A SHELL BUILDING UNDER FBC
 13-101.1.6. UNLESS THE BUILDING IS COMPLETED AS PER ALL
 ASSUMPTIONS MADE IN THE ORIGINAL CODE COMPLIANCE
 SUBMITTAL, A REVISED CODE SUBMITTAL(S) USING METHODS A,
 B OR C SHALL BE SUBMITTED WHEN COMPLETION OF THE
 BUILDING (OR PART OF THE BUILDING) IS PERMITTED.
  
 3. M1: EQUIPMENT SCHEDULE SHOWS A TOTAL OF OUTDOOR AIR
 FOR ALL 8 SYSTEMS TO BE 1640 CFM. THE OUTDOOR AIR
 CALCULATIONS BOX SHOWS A TOTAL OF 1760 CFM. WHICH IS
 CORRECT? PLEASE COORDINATE SCHEDULE WITH CALCULATIONS.
  
 4. M1 OUTDOOR AIR CALCULATIONS: PLAN REFERENCES ASHRAE
 62-99. THE CORRECT REFERENCE STANDARD AS OF DECEMBER 8,
 2006 IS ASHRAE 62.1-2004. THE 2004 FBC ALLOWS
 COMPLIANCE WITH EITHER FBC,M SEC 403.3 OR ASHRAE
 62.1-2004. PLEASE DECLARE ON PLANS WHICH METHOD OF
 COMPLIANCE IS TO BE USED AND VERIFY THAT THE RATES AND
 CALCULATIONS COMPLY WITH THE METHOD BEING EMPLOYED.
  
 5. M1 THROUGH M7: THE COA NUMNER OF THE ENGINEERING
 BUISENESS DOES NOT APPEAR ON PLANS. PLEASE SEE FAC RULE
 61G15-23.002(2) "IF PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS, ENGINEERS SHALL
 LEGIBLY INDICATE THEIR NAME AND LICENSE NUMBER, AS WELL
 AS, THE NAME, ADDRESS, AND CERTIFICATE OF AUTHORIZATION
 NUMBER OF THE ENGINEERING BUSINESS ON EACH SHEET. A
 TITLE BLOCK ON EACH SHEET CONTAINING THE PRINTED NAME,
 ADDRESS, AND LICENSE NUMBER OF THE ENGINEER OR IF
 APPLICABLE, THE NAME AND LICENSE NUMBER OF THE
 ENGINEER, AND THE NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING BUSINESS WILL
 SATISFY THIS REQUIREMENT."
  
 6. VERIFY THAT PROVISIONS HAVE BEEN MADE TO PROVIDE THE
 REQUIRED 250 CFM OF VENTILATION FOR TOILET ROOMS PER
 FBC,M TABLE 403.3. ALSO, PROVISIONS SHALL BE MADE TO
 ASSURE ALL AIR SUPPLIED TO TOILET ROOMS IS EXHAUSTED IN
 ACCORDANCE WITH FBC,M 403.2.1.
  
 7. M2 THROUGH M5: WHAT IS THE SOURCE OF OUTDOOR AIR
 PROVIDED FOR ALL SPACES? NONE COULD BE FOUND ON PLANS.
 PLEASE SHOW THE SOURCE OF OUTDOOR AIR ON PLANS AND HOW
 IT IS TO BE INTRODUCED INTO THE SPACE. FBC,M 403.3
  
 8. BY WHAT MEANS WILL AIR BE EXHAUSTED FROM THE SPACE
 TO PROVIDE FOR THE INTRODUCTION OF THE REQUIRED AMOUNT
 OF OUTDOOR AIR? THE AMOUNT OF SUPPLY AIR SHALL BE
 APPROXIMATELY EQUAL TO THE AMOUNT OF EXHAUST AND RETURN
 AIR PER FBC,M 403.1.
  
 9. VENTILATION SYSTEMS SHALL BE DESIGNED TO BE CAPABLE
 OF REDUCING THE SUPPLY OF OUTDOOR AIR TO THE MINIMUM
 VENTILATION RATES REQUIRED BY SECTION 6.1.3 OF ASHRAE
 62. SYSTEMS MAY BE DESIGNED TO SUPPLY OUTSIDE AIR
 QUANTITIES EXCEEDING MINIMUM LEVELS, BUT THEY SHALL BE
 CAPABLE OF OPERATING AT NO MORE THAN MINIMUM LEVELS
 THROUGH THE USE OF RETURN DUCTS, MANUALLY OR
 AUTOMATICALLY OPERATED CONTROL DAMPERS, FAN VOLUME
 CONTROLS, OR OTHER DEVICES. FBC 13-409.1.ABC.1.1
  
 10. PROVIDE AN AIR BALANCE SCHEDULE TO SHOW THE SPACE
 TO BE PRESSURIZED WITH RESPECT TO THE OUTDOORS PER FBC
 13-409.1.ABC.2.
  
 11. ONCE THE SOURCE OF OUTDOOR AIR IS DETERMINED (SEE
 COMMENT #7), SHOW DAMPER SHUTOF CONTROLS AS REQUIRED BY
 FBC 13-409.1.ABC.3.3. IF MOTORIZED DAMPERS ARE USED,
 PROVIDE SUBMITTAL DATA SHOWING LEAKAGE RATES TO BE IN
 COMPLIANCE WITH FBC 13-409.1.ABC.3.4.
  
 12. SEVERAL AREAS ON FLOOR PLAN, SUCH AS THE HIGH
 OCCUPANCY CONFERENCE AND TRAINING ROOMS, ARE NOT
 DESIGNED FOR THE INTRODUCTION OF OUTDOOR AIR FOR
 VENTILATION. EXAMPLE: CONFERENCE ROOM SHOWS 1200 CFM OF
 SUPPLY AND 1200 CFM OF RETURN. HOW IS IT THAT THE
 REQUIRED 500 CFM OF OUTDOOR AIR IS TO BE SUPPLIED INTO
 THE SPACE? SEE COMMENT #9.
  
 13. UNITS AC 1, AC 2, AC 4, AC 6 AND AC 8 ARE SHOWN
 WITH A COMMON RETURN AIR PLENUM. WHERE MULTIPLE
 AIR-HANDLING SYSTEMS SHARE COMMON SUPPLY OR RETURN AIR
 DUCTS OR PLENUMS WITH A COMBINED DESIGN CAPACITY
 GREATER THAN 2,000 CFM, THE RETURN AIR AND SUPPLY AIR
 SYSTEM SHALL BE PROVIDED WITH SMOKE DETECTORS IN
 ACCORDANCE WITH SECTION 606.2.1. DUCT SMOKE DETECTORS
 SHALL BE CONNECTED TO THE BUILDING FIRE ALARM SYSTEM
 PER FBC,M 606.4.1
  
 14. M6: THERE ARE 8 CONDENSERS ON ROOF TO SERVE THE 2ND
 FLOOR, BUT THERE ARE ONLY 7 LINE SETS SHOWN ON PLAN.
 PLEASE CLARIFY.
  
 15. M7: ARE CONDENSERS TO BE MOUNTED ON INDIVIDUAL
 PRE-ENGINEERED A/C STANDS AS SHOWN ON CU MOUNTING
 DETAIL OR A RACK WHICH IS BEING PROVIDED BY THE BASE
 BUILDING? IF PRE-ENGINEERED STANDS ARE TO BE USED,
 PROVIDE CURRENT PRODUCT APPROVALS FOR THE SPECIFIC
 STANDS TO BE USED PER FAC RULE 9B-72. IF USING BASE
 BUILDING RACK, PROVIDE ENGINEERING SHOWING HOW
 CONDENSERS ARE TO BE ATTACHED TO THIS RACK TO MEET WIND
 LOAD REQUIREMENTS PER FBC,M 301.13 AND FBC CH 16.
 PROVIDE WIND LOAD CALCULATIONS.
  
 16. M7: CONDENSATE TRAP DETAIL, CHECK THE EQUIPMENT
 MANUFACTURER'S REQUIREMENTS FOR TRAPS AS ALL CONDENSATE
 DRAINS SHALL BE TRAPPED AS REQUIRED BY THE EQUIPMENT
 MANUFACTURER. FBC,M 307.2.4
  
 17. ENERGY CALCULATIONS: PROJECT SUMMARY SHOWS MAX
 TONNAGE AT ZERO. PLEASE CORRECT. ALSO, PLEASE INCLUDE
 COOLING LOAD CALCULATIONS AND THE INPUT DATA REPORT.
  