| 2007-09-05 13:32:41 | *****DENIED***** |
| | |
| | |
| | 01.THE LOCATION OF THE PROJECT AS INDICATED ON THE |
| | LOCATION MAP (COVER SHEET) IS ILLEGIBLE. |
| | |
| | 02.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. |
| | |
| | 03.THIS PROJECT IS LISTED AS A NEW BUSINESS |
| | OCCUPANCY.IS THIS PROJECTED SCOPE OF WORK A CHANGE OF |
| | OCCUPANCY? |
| | |
| | 04.IT APPEARS THAT THIS BUILDOUT WILL COMPRISE OF THE |
| | ENTIRE SECOND FLOOR.IF A SUITE NUMBER IS ASSIGNED TO |
| | THIS SITE,THE SUITE NEMBER SHALL BE INCLUDED IN THE |
| | ADDRESS LOCATED IN THE TITLE BLOCK OF EACH SUBMITTED |
| | PLAN SHEET. |
| | |
| | 05.COULD NOT LOCATE SHEET A135.1 AS INDICATED IN THE |
| | SHEET INDEX OF THE COVER SHEET. |
| | |
| | 06.IN THE EVENT OF A FIRE, STAIRWELLS INSTEAD OF THE |
| | ELEVATORS WILL BE USED.PLEASE EXPLAIN RATIONALE FOR |
| | GOING THROUGH THE CONFERENCE ROOM OR GOING THROUGH THE |
| | BREAK ROOM TO ACCESS THOSE FIRE-RATED STAIRWELLS. |
| | |
| | 07.ACCESS TO AN EXIT SHALL NOT BE THROUGH ROOMS OR |
| | SPACES SUBJECT TO LOCKING. |
| | |
| | 08.SEPARATE PLANS AND PERMIT WILL BE REQUIRED FOR |
| | ACCESS CONTROL SYSTEM ENTRANCE/EGRESS DOORS. |
| | |
| | 09.ON SHEET A120.1, THE SUPPLY CLOSET DOOR OPENS INTO |
| | THE PATH OF EGRESS.DURING ITS SWING, ANY DOOR IN A |
| | MEANS OF EGRESS SHALL LEAVE NOT LESS THAN ONE-HALF OF |
| | THE REQUIRED WIDTH OF AN AISLE, A CORRIDOR, OR |
| | PASSAGEWAY. |
| | |
| | 10.HOW DOES A PERSON(S) GET IN OR OUT OF THE MODULAR |
| | OFFICES? |
| | |
| | 11.ON SHEET A120.1, IT IS SHOWN THAT THE DOUBLE DOORS |
| | (NEAR THE RECEPTION AREA) SWING OPPOSITE THE DIRECTION |
| | OF EGRESS TRAVEL.PLEASE EXPLAIN. |
| | |
| | 12.WILL THE SCOPE OF WORK IMPACT THE FIRE SPRINKLER |
| | LAYOUT CURRENTLY ON THE FLOOR?IF SO, SEPARATE PLANS |
| | AND PERMIT WILL BE REQUIRED FOR THE SPRINKLER REMODEL |
| | |
| | 13.SEPARATE PLANS AND PERMIT WILL BE REQUIRED FOR THE |
| | FIRE ALARM INSTALLATION OR REMODEL. |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED |
| | |
| | |
| | CAPT. MICHAEL A. WILLIAMS |
| | FIRE PLAN REVIEW |