Plan Review Notes
Plan Review Notes For Permit 07070482
Permit Number 07070482
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-09-05 13:32:41*****DENIED*****
  
  
 01.THE LOCATION OF THE PROJECT AS INDICATED ON THE
 LOCATION MAP (COVER SHEET) IS ILLEGIBLE.
  
 02.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 03.THIS PROJECT IS LISTED AS A NEW BUSINESS
 OCCUPANCY.IS THIS PROJECTED SCOPE OF WORK A CHANGE OF
 OCCUPANCY?
  
 04.IT APPEARS THAT THIS BUILDOUT WILL COMPRISE OF THE
 ENTIRE SECOND FLOOR.IF A SUITE NUMBER IS ASSIGNED TO
 THIS SITE,THE SUITE NEMBER SHALL BE INCLUDED IN THE
 ADDRESS LOCATED IN THE TITLE BLOCK OF EACH SUBMITTED
 PLAN SHEET.
  
 05.COULD NOT LOCATE SHEET A135.1 AS INDICATED IN THE
 SHEET INDEX OF THE COVER SHEET.
  
 06.IN THE EVENT OF A FIRE, STAIRWELLS INSTEAD OF THE
 ELEVATORS WILL BE USED.PLEASE EXPLAIN RATIONALE FOR
 GOING THROUGH THE CONFERENCE ROOM OR GOING THROUGH THE
 BREAK ROOM TO ACCESS THOSE FIRE-RATED STAIRWELLS.
  
 07.ACCESS TO AN EXIT SHALL NOT BE THROUGH ROOMS OR
 SPACES SUBJECT TO LOCKING.
  
 08.SEPARATE PLANS AND PERMIT WILL BE REQUIRED FOR
 ACCESS CONTROL SYSTEM ENTRANCE/EGRESS DOORS.
  
 09.ON SHEET A120.1, THE SUPPLY CLOSET DOOR OPENS INTO
 THE PATH OF EGRESS.DURING ITS SWING, ANY DOOR IN A
 MEANS OF EGRESS SHALL LEAVE NOT LESS THAN ONE-HALF OF
 THE REQUIRED WIDTH OF AN AISLE, A CORRIDOR, OR
 PASSAGEWAY.
  
 10.HOW DOES A PERSON(S) GET IN OR OUT OF THE MODULAR
 OFFICES?
  
 11.ON SHEET A120.1, IT IS SHOWN THAT THE DOUBLE DOORS
 (NEAR THE RECEPTION AREA) SWING OPPOSITE THE DIRECTION
 OF EGRESS TRAVEL.PLEASE EXPLAIN.
  
 12.WILL THE SCOPE OF WORK IMPACT THE FIRE SPRINKLER
 LAYOUT CURRENTLY ON THE FLOOR?IF SO, SEPARATE PLANS
 AND PERMIT WILL BE REQUIRED FOR THE SPRINKLER REMODEL
  
 13.SEPARATE PLANS AND PERMIT WILL BE REQUIRED FOR THE
 FIRE ALARM INSTALLATION OR REMODEL.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved