| Date |
Text |
| 2007-08-13 11:12:35 | ** DENIED ** |
| | |
| | |
| | |
| | 1) NOTE: PLEASE KNOW THAT AS OF THIS REVIEW AND DATE |
| | THE CO ON THE BASE SHELL BUILDING AHS NOT BEEN |
| | ACHIEVED. ANY DESIGN CHANGES FOR KNOWN LOADS ON THE |
| | SERVICE, KNOWN LOADS ON THE ENERGY CALCULATIONS AND |
| | CHANGES TO THE BASE BUILDING ELECTRICAL SYSTEM WILL BE |
| | REQUIRED ON THE BASE BUILDING PLANS BEFORE THE PERMIT |
| | FOR CONSTRUCTION CAN BE ISSUED. |
| | PLEASE KNOW THAT IF THE INTENT IS TO PERMIT THIS SCOPE |
| | OF WORK BEFORE THE CO OF THE SHELL ALL OF THE ABOVE |
| | ITEMS MUST BE ADDRESSED ON THOSE PLANS AND SUPPORTING |
| | DOCUMENTS BEFORE THE CO CAN BE ISSUED. |
| | IF CO IS OBTAINED BEFORE PERMIT ISSUANCE OF BUILD OUT |
| | THEN THIS WOULD BE OK AS IS. |
| | PLEASE ALSO KNOW THAT ANY BUILD OUT WORK WHICH IS DONE |
| | ON THE SHELL BUILDING BEFORE ISSUANCE OF CO IS STILL TO |
| | BE UNDER THE REVIEW OF THE BASE BUILDING ARCHITECT AND |
| | ENGINEERING FIRM(S). THIS HAS BEEN CONFIRMED WITH THE |
| | STATE AND THE BUILDING OFFICIAL AS THE BUILDING IS |
| | STILL UNDER THE BASE DESIGN TEAMS RESPONSIBILITY. |
| | |
| | 2) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH |
| | ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS |
| | UNDER THE NEW CODES ADOPTED BY THE STATE. |
| | PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO |
| | THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. |
| | PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY |
| | AFFECT DESIGNS FOR ALL TRADES. |
| | PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS |
| | REVIEWER AT A MINIMUM. |
| | 2004 FBC W/ 2006 REVISIONS |
| | 2005 NFPA-70 |
| | 2002 NFPA-72 |
| | 2003 NFPA-101 |
| | |
| | 3) NOTE: PLEASE SEE MISSING CERTIFICATE OF |
| | AUTHORIZATION NUMBER ON TITLE BLOCKS OF MEP PLANS AS |
| | REQUIRED PER FLORIDA ADMINISTRATIVE CODE 61G15-23.002 |
| | AND FLORIDA STATUTES 471.023. |
| | THIS IS REQUIRED FOR ALL SHEETS AND FOR ALL TRADES |
| | WHETHER OR NOT COMMENT IS MADE BY OTHER TRADES. |
| | |
| | 4) NOTE: PLEASE SEE THE ENERGY CALCULATIONS AS |
| | SUBMITTED ARE NOT COMPLETE AT THIS TIME FOR COMPLETE |
| | REVIEW. PLEASE SEE THE SHEETS ARE MISSING THE INPUT |
| | DATA REPORTS FOR REVIEW AND COORDINATION WITH PLANS. |
| | PLEASE SEE SHEET 2 OF THE SUMMARY SHEETS WHICH STATES |
| | THE INPUT DATA REPORTS MUST ACCOMPANY THE SUMMARY |
| | SHEETS. |
| | PLEASE BE SURE THE FIXTURE LEGEND COORDINATES WITH THE |
| | CALCULATIONS FOR TYPE OF FIXTURES, WATTAGES, NUMBER OF |
| | FIXTURES ETC. |
| | 13-415.1.A, 13-415.2, 13-103.1.1.1. |
| | PLEASE ALSO BE SURE THE OWNER AGENT IS SIGNED ON. |
| | |
| | 5) NOTE: PLEASE SEE THE FLOOR LAYOUT SEEMS TO SHOW WHAT |
| | APPEARS TO BE COMMON AREA INCLUDING : ELEVATOR LOBBY, |
| | BATHROOMS, EXIT STAIR ACCESS, ELECTRICAL ROOM ETC YET |
| | THE PLANS INDICATE CIRCUITING FROM THE TENANT |
| | ELECTRICAL?? |
| | PLEASE SEE IF THESE ARE COMMONS AREAS, THEY ARE |
| | REQUIRED TO BE FED FROM HOUSE PANELS. |
| | PLEASE ALSO SEE NO CIRCUITING IS BEING SHOWN ON |
| | BATHROOMS WHEN THE PLANS CLEARLY SHOWS THIS AS ALL ONE |
| | TENANT SPACE ALONG WITH NOTE #9 ON E-1 WHICH MENTIONS |
| | CONTROLS FOR BATHROOMS.? |
| | PLEASE CLARIFY THE SERVICE AS SHOWN AS THE PLANS ARE |
| | FOR ONE TENANT AND RISER SHOWS EACH PANEL ON ITS OWN |
| | METER. THIS SCENARIO IS NOT PERMITTED AT THIS TIME AS |
| | THIS IS ONE TENANT AND ONE METER IS PERMITTED. |
| | PLEASE SEE SHEET E-2 WHICH CLEARLY STATES TO SEE |
| | EXISTING ELECTRICAL ROOM LAYOUT ON E-5, YET THERE WAS |
| | NO E-5 SUBMITTED? |
| | HOUSE AND MAIN POWER MAY NOT BE LOCATED IN THE TENANT |
| | SPACE. |
| | THIS INFORMATION WILL ALSO BE FORWARDED TO THE FIRE |
| | MARSHAL, ZONING AND BUILDING REVIEWS AS THE USE OF |
| | MULTIPLE METERS FOR ONE TENANT IS NOT PERMITTED. |
| | REVISING THE RISER WILL BE NEEDED. 215.5, 230.70, |
| | 230.2, 240.24,ETC. |
| | FBC 106.1.2 AND 106.3.5.1.2 FOR ADDITIONAL INFORMATION. |
| | THERE ARE TOO MANY UNKNOWNS AT THIS TIME FOR DETAILED |
| | REVIEW. |
| | |
| | 6) NOTE: PLEASE SEE MISSING REQUIRED DISCONNECTING |
| | MEANS FOR ELECTRICAL IN SERVER ROOM. THIS AS SHOWN |
| | APPEARS TO BE AN IT ROOM AND NEED MORE INFORMATION ON |
| | EQUIPMENT BEING INSTALLED AND PROPOSED FOR ROOM. UPS, |
| | EQUIPMENT ETC. |
| | PLEASE SUBMIT MANUFACTURES SPECS/CUT SHEETS FOR ANY |
| | EQUIPMENT BEING INSTALLED. 110.3, 90.7 |
| | PLEASE SEE 645.10,645.11, 645.4 |
| | PLEASE SEE 645.5A FOR BRANCH CIRCUITS. |
| | PLEASE KNOW AT THIS TIME AS THE ROOM IS SHOWN THIS IS |
| | BEING CONSIDERED AS AN IT ROOM AND WILL NEED THE 1HR |
| | RATING OF WALLS AND DISCONNECTING MEANS FOR EQUIPMENT |
| | INCLUDING THE DEDICATED A/C. |
| | NFPA-75 |
| | FBC 106.1.2 |
| | |
| | 7) NOTE: PLEASE SEE 605.6, 605.7, 608.8D ETC FOR |
| | REQUIRED INFORMATION AND BREAKERS FOR MODULAR |
| | FURNITURE. |
| | |
| | 8) NOTE: PLEASE KNOW THAT EVEN AS LOW VOLTAGE FOR |
| | PHONE/DATA IS SHOWN ON PLANS, THESE WILL STILL BE |
| | REQUIRED TO BE UNDER A SEPARATE PERMIT. THEPLANS MAY |
| | BE REFERENCED FOR A TURN AROUND PERMIT AS LONG AS THE |
| | PLANS INDICATE ALL LOW VOLTAGE AS APPLIED. |
| | PLEASE KNOW FEES WILL BE DUE BASED ON LV SCOPE. |
| | THIS NOTE IS ONLY FOR INFORMATIONAL PURPOSES ONLY AND |
| | NO INFORMATION NEEDS TO BE PLACED ON PLANS. |
| | |
| | 9) NOTE: PLEASE SUPPLY MORE INFORMATION ON CHAPTER 13 |
| | 13-415.1.ABC.1.1, AND .1.2. |
| | PLEASE BE SURE ALL MAXIMUM TIMES ARE STATED FOR EACH |
| | DEVICE AS CHOSEN. |
| | PLEASE SEE SOME AREAS WHICH STILL CONTAIN ONLY A |
| | STANDARD WALL SWITCH AS LISTED ON SYMBOL LEGEND. |
| | (EXAMPLE SEE SUPPLY CLOSET) |
| | |
| | |
| | 10 ) NOTE: PLEASE SEE FBC 2004 11-4.28.1, .2 AND .3(4) |
| | AND STATE THE MINIMUM HORN, STROBE LEVELS ON PLANS FOR |
| | ADA REQUIRED AREAS. DEVICES ARE BEING SHOWN ON |
| | PLANS/LEGEND. PLEASE CORRELATE WITH PLANS, AND FA |
| | SHEETS SUBMITTED. |
| | ** PLEASE KNOW THAT THE FIRE ALARM WILL BE UNDER A |
| | SEPARATE PERMIT HOWEVER THE BASE LIFE SAFETY SYSTEM IS |
| | REQUIRED ON BASE PLANS AS SHOWN. DO NOT REMOVE FROM |
| | SETS. |
| | FBC 106.3.5.1.2 |
| | |
| | 11) NOTE: PLEASE KNOW THAT THE PLANS NEED TO LABEL AND |
| | PROVIDE ROOM AND AREA DESIGNATIONS ON PLANS AND |
| | CORRELATE WITH THE PANEL SCHEDULES SHOWING ALL ROOMS |
| | AND AREAS IN WHICH CIRCUITS FEED WILL BE REQUIRED FOR |
| | EACH PANEL.PLEASE KNOW THAT A NUMERICAL DESIGNATION |
| | MAY BE USED. (EXAMPLE OFFICE 103, OFFICE 105 ETC) |
| | PLEASE SEE TEXT WHICH IS TAKEN FROM COMMENTARY IN THE |
| | CODE WHICH STATES THE USE OF *GEN LT* ETC IS NOT |
| | ACCEPTABLE. |
| | |
| | *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE |
| | THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A |
| | PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE |
| | THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED. |
| | CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED |
| | AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE |
| | BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN, |
| | DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE |
| | CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT |
| | ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS |
| | ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR |
| | RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT |
| | OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE |
| | ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT |
| | PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS |
| | SECTION.* |
| | 408.4, 310.16, 240.4 ETC |
| | FBC 106.3.5.4 |
| | |
| | 12) NOTE: PLEASE OBTAIN INFORMATION FROM THE BASE |
| | BUILDING PLANS AS THE FEEDERS AS SHOWN THIS RISER AS |
| | EXISTING IS NOT ACCURATE WITH THE PLANS ON BASE |
| | BUILDING. THESE WERE REVISED. |
| | FBC 106.1.2 |
| | |
| | 13) NOTE: PLEASE DO NOT STAPLE AND ATTACH SUPPORTING |
| | DOCUMENTS DOWN THE SIDE OF PLANS. THE SUPPORTING |
| | DOCUMENTS SHOULD BE ATTACHED INTO EACH SET OF THEIR OWN |
| | FOR REVIEW. |
| | FBC 106.1 |
| | |
| | 14) NOTE: PLANS WILL BE ROUTED TO ADDRESSING AS A |
| | SUITE/UNIT NUMBER WILL NEED TO BE DETERMINED. |
| | ONCE THIS HAS BEEN DETERMINED PLEASE BE SURE TO PLANS |
| | ON TITLE BLOCK OF PLANS. |
| | AT THIS TIME NONE HAS BEEN ASSIGNED. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |