Plan Review Notes
Plan Review Notes For Permit 07070482
Permit Number 07070482
Review Stop E
Sequence Number 1
Notes
Date Text
2007-08-13 11:12:35** DENIED **
  
  
  
 1) NOTE: PLEASE KNOW THAT AS OF THIS REVIEW AND DATE
 THE CO ON THE BASE SHELL BUILDING AHS NOT BEEN
 ACHIEVED. ANY DESIGN CHANGES FOR KNOWN LOADS ON THE
 SERVICE, KNOWN LOADS ON THE ENERGY CALCULATIONS AND
 CHANGES TO THE BASE BUILDING ELECTRICAL SYSTEM WILL BE
 REQUIRED ON THE BASE BUILDING PLANS BEFORE THE PERMIT
 FOR CONSTRUCTION CAN BE ISSUED.
 PLEASE KNOW THAT IF THE INTENT IS TO PERMIT THIS SCOPE
 OF WORK BEFORE THE CO OF THE SHELL ALL OF THE ABOVE
 ITEMS MUST BE ADDRESSED ON THOSE PLANS AND SUPPORTING
 DOCUMENTS BEFORE THE CO CAN BE ISSUED.
 IF CO IS OBTAINED BEFORE PERMIT ISSUANCE OF BUILD OUT
 THEN THIS WOULD BE OK AS IS.
 PLEASE ALSO KNOW THAT ANY BUILD OUT WORK WHICH IS DONE
 ON THE SHELL BUILDING BEFORE ISSUANCE OF CO IS STILL TO
 BE UNDER THE REVIEW OF THE BASE BUILDING ARCHITECT AND
 ENGINEERING FIRM(S). THIS HAS BEEN CONFIRMED WITH THE
 STATE AND THE BUILDING OFFICIAL AS THE BUILDING IS
 STILL UNDER THE BASE DESIGN TEAMS RESPONSIBILITY.
  
 2) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH
 ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS
 UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 3) NOTE: PLEASE SEE MISSING CERTIFICATE OF
 AUTHORIZATION NUMBER ON TITLE BLOCKS OF MEP PLANS AS
 REQUIRED PER FLORIDA ADMINISTRATIVE CODE 61G15-23.002
 AND FLORIDA STATUTES 471.023.
 THIS IS REQUIRED FOR ALL SHEETS AND FOR ALL TRADES
 WHETHER OR NOT COMMENT IS MADE BY OTHER TRADES.
  
 4) NOTE: PLEASE SEE THE ENERGY CALCULATIONS AS
 SUBMITTED ARE NOT COMPLETE AT THIS TIME FOR COMPLETE
 REVIEW. PLEASE SEE THE SHEETS ARE MISSING THE INPUT
 DATA REPORTS FOR REVIEW AND COORDINATION WITH PLANS.
 PLEASE SEE SHEET 2 OF THE SUMMARY SHEETS WHICH STATES
 THE INPUT DATA REPORTS MUST ACCOMPANY THE SUMMARY
 SHEETS.
 PLEASE BE SURE THE FIXTURE LEGEND COORDINATES WITH THE
 CALCULATIONS FOR TYPE OF FIXTURES, WATTAGES, NUMBER OF
 FIXTURES ETC.
 13-415.1.A, 13-415.2, 13-103.1.1.1.
 PLEASE ALSO BE SURE THE OWNER AGENT IS SIGNED ON.
  
 5) NOTE: PLEASE SEE THE FLOOR LAYOUT SEEMS TO SHOW WHAT
 APPEARS TO BE COMMON AREA INCLUDING : ELEVATOR LOBBY,
 BATHROOMS, EXIT STAIR ACCESS, ELECTRICAL ROOM ETC YET
 THE PLANS INDICATE CIRCUITING FROM THE TENANT
 ELECTRICAL??
 PLEASE SEE IF THESE ARE COMMONS AREAS, THEY ARE
 REQUIRED TO BE FED FROM HOUSE PANELS.
 PLEASE ALSO SEE NO CIRCUITING IS BEING SHOWN ON
 BATHROOMS WHEN THE PLANS CLEARLY SHOWS THIS AS ALL ONE
 TENANT SPACE ALONG WITH NOTE #9 ON E-1 WHICH MENTIONS
 CONTROLS FOR BATHROOMS.?
 PLEASE CLARIFY THE SERVICE AS SHOWN AS THE PLANS ARE
 FOR ONE TENANT AND RISER SHOWS EACH PANEL ON ITS OWN
 METER. THIS SCENARIO IS NOT PERMITTED AT THIS TIME AS
 THIS IS ONE TENANT AND ONE METER IS PERMITTED.
 PLEASE SEE SHEET E-2 WHICH CLEARLY STATES TO SEE
 EXISTING ELECTRICAL ROOM LAYOUT ON E-5, YET THERE WAS
 NO E-5 SUBMITTED?
 HOUSE AND MAIN POWER MAY NOT BE LOCATED IN THE TENANT
 SPACE.
 THIS INFORMATION WILL ALSO BE FORWARDED TO THE FIRE
 MARSHAL, ZONING AND BUILDING REVIEWS AS THE USE OF
 MULTIPLE METERS FOR ONE TENANT IS NOT PERMITTED.
 REVISING THE RISER WILL BE NEEDED. 215.5, 230.70,
 230.2, 240.24,ETC.
 FBC 106.1.2 AND 106.3.5.1.2 FOR ADDITIONAL INFORMATION.
 THERE ARE TOO MANY UNKNOWNS AT THIS TIME FOR DETAILED
 REVIEW.
  
 6) NOTE: PLEASE SEE MISSING REQUIRED DISCONNECTING
 MEANS FOR ELECTRICAL IN SERVER ROOM. THIS AS SHOWN
 APPEARS TO BE AN IT ROOM AND NEED MORE INFORMATION ON
 EQUIPMENT BEING INSTALLED AND PROPOSED FOR ROOM. UPS,
 EQUIPMENT ETC.
 PLEASE SUBMIT MANUFACTURES SPECS/CUT SHEETS FOR ANY
 EQUIPMENT BEING INSTALLED. 110.3, 90.7
 PLEASE SEE 645.10,645.11, 645.4
 PLEASE SEE 645.5A FOR BRANCH CIRCUITS.
 PLEASE KNOW AT THIS TIME AS THE ROOM IS SHOWN THIS IS
 BEING CONSIDERED AS AN IT ROOM AND WILL NEED THE 1HR
 RATING OF WALLS AND DISCONNECTING MEANS FOR EQUIPMENT
 INCLUDING THE DEDICATED A/C.
 NFPA-75
 FBC 106.1.2
  
 7) NOTE: PLEASE SEE 605.6, 605.7, 608.8D ETC FOR
 REQUIRED INFORMATION AND BREAKERS FOR MODULAR
 FURNITURE.
  
 8) NOTE: PLEASE KNOW THAT EVEN AS LOW VOLTAGE FOR
 PHONE/DATA IS SHOWN ON PLANS, THESE WILL STILL BE
 REQUIRED TO BE UNDER A SEPARATE PERMIT. THEPLANS MAY
 BE REFERENCED FOR A TURN AROUND PERMIT AS LONG AS THE
 PLANS INDICATE ALL LOW VOLTAGE AS APPLIED.
 PLEASE KNOW FEES WILL BE DUE BASED ON LV SCOPE.
 THIS NOTE IS ONLY FOR INFORMATIONAL PURPOSES ONLY AND
 NO INFORMATION NEEDS TO BE PLACED ON PLANS.
  
 9) NOTE: PLEASE SUPPLY MORE INFORMATION ON CHAPTER 13
 13-415.1.ABC.1.1, AND .1.2.
 PLEASE BE SURE ALL MAXIMUM TIMES ARE STATED FOR EACH
 DEVICE AS CHOSEN.
 PLEASE SEE SOME AREAS WHICH STILL CONTAIN ONLY A
 STANDARD WALL SWITCH AS LISTED ON SYMBOL LEGEND.
 (EXAMPLE SEE SUPPLY CLOSET)
  
  
 10 ) NOTE: PLEASE SEE FBC 2004 11-4.28.1, .2 AND .3(4)
 AND STATE THE MINIMUM HORN, STROBE LEVELS ON PLANS FOR
 ADA REQUIRED AREAS. DEVICES ARE BEING SHOWN ON
 PLANS/LEGEND. PLEASE CORRELATE WITH PLANS, AND FA
 SHEETS SUBMITTED.
 ** PLEASE KNOW THAT THE FIRE ALARM WILL BE UNDER A
 SEPARATE PERMIT HOWEVER THE BASE LIFE SAFETY SYSTEM IS
 REQUIRED ON BASE PLANS AS SHOWN. DO NOT REMOVE FROM
 SETS.
 FBC 106.3.5.1.2
  
 11) NOTE: PLEASE KNOW THAT THE PLANS NEED TO LABEL AND
 PROVIDE ROOM AND AREA DESIGNATIONS ON PLANS AND
 CORRELATE WITH THE PANEL SCHEDULES SHOWING ALL ROOMS
 AND AREAS IN WHICH CIRCUITS FEED WILL BE REQUIRED FOR
 EACH PANEL.PLEASE KNOW THAT A NUMERICAL DESIGNATION
 MAY BE USED. (EXAMPLE OFFICE 103, OFFICE 105 ETC)
 PLEASE SEE TEXT WHICH IS TAKEN FROM COMMENTARY IN THE
 CODE WHICH STATES THE USE OF *GEN LT* ETC IS NOT
 ACCEPTABLE.
  
 *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE
 THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A
 PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE
 THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED.
 CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED
 AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE
 BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN,
 DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE
 CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT
 ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS
 ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR
 RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT
 OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE
 ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT
 PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS
 SECTION.*
 408.4, 310.16, 240.4 ETC
 FBC 106.3.5.4
  
 12) NOTE: PLEASE OBTAIN INFORMATION FROM THE BASE
 BUILDING PLANS AS THE FEEDERS AS SHOWN THIS RISER AS
 EXISTING IS NOT ACCURATE WITH THE PLANS ON BASE
 BUILDING. THESE WERE REVISED.
 FBC 106.1.2
  
 13) NOTE: PLEASE DO NOT STAPLE AND ATTACH SUPPORTING
 DOCUMENTS DOWN THE SIDE OF PLANS. THE SUPPORTING
 DOCUMENTS SHOULD BE ATTACHED INTO EACH SET OF THEIR OWN
 FOR REVIEW.
 FBC 106.1
  
 14) NOTE: PLANS WILL BE ROUTED TO ADDRESSING AS A
 SUITE/UNIT NUMBER WILL NEED TO BE DETERMINED.
 ONCE THIS HAS BEEN DETERMINED PLEASE BE SURE TO PLANS
 ON TITLE BLOCK OF PLANS.
 AT THIS TIME NONE HAS BEEN ASSIGNED.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717