Plan Review Notes
Plan Review Notes For Permit 07070482
Permit Number 07070482
Review Stop B
Sequence Number 1
Notes
Date Text
2007-08-17 14:39:461920 WEKIVA WAY 2ND FLOOR BUILD-OUT
  
  
 PERMIT: 07070482
 ADD: 1920 WEKIVA WAY
 CONT: ANDERSON-MOORE CONSTRUCTION
 ? THE CAPITAL CITY OF THE PALM BEACHES?
 TEL: (561)662-1819
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3)PLEASE PROVIDE THE OCCUPANT LOAD THAT WILL BE GOING
 THROUGH VARIOUS DOORS. IT APPEARS THAT
 SOME OF THE DOORS MAY HAVE AN OCCUPANT LOAD GREATER
 THAN 50 REQUIRINGTHE DOOR TO SWING IN THE DIRECTION
 OF EGRESS TRAVEL SEE 1008.1.2 AND 1002.1 (DEFINITIONS)
 OCCUPANT LOAD.
  
 4) SHEET A2.10.1THE BREAK ROOM SINK AND THE
 CONFERENCE ROOM SINK WILL BOTH REQUIRE THE FOLLOWING:
 SINKS:
 11-4.24.2 SINKS, HEIGHT. SINKS SHALL BE MOUNTED WITH
 THE COUNTER NO HIGHER THAN 34" ABOVE THE FINISH FLOOR.
 11-4.24.3 KNEE CLEARANCE THAT IS AT LEAST 27" HIGH 30"
 WIDE, AND 19" DEEP SHALL BE PROVIDED UNDERNEATH SINKS.
 11-4.24.5 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE AT
 LEAST 30 INCHES BY 48 INCHES (760 MM BY 1219 MM)
 COMPLYING WITH SECTION 11-4.2.4 SHALL BE PROVIDED IN
 FRONT OF A SINK TO ALLOW FORWARD APPROACH. THE CLEAR
 FLOOR SPACE SHALL BE ON AN ACCESSIBLE ROUTE AND SHALL
 EXTEND A MAXIMUM OF 19 INCHES (485 MM) UNDERNEATH THE
 SINK.
  
 5) SHEET A125.2 DOOR # 9 IS MISSING THE 18? ON THE
 LATCH SIDE OF THE DOOR. 11-4.13.6 MANEUVERING
 CLEARENCES AT DOORS. MINIMUM MANEUVERING CLEARANCES
 AT DOORS THAT ARE NOT AUTOMATIC OR POWER-ASSISTED SHALL
 BE AS SHOWN IN FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARANCES SHALL BE CLEAR & LEVEL.
 6) SHEET A125.3 DOOR# 19 IS ALSO MISSING THE REQUIRED
 18? AT THE LATCH SIDE. 11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARANCES
 AT DOORS THAT ARE NOT AUTOMATIC OR POWER-ASSISTED SHALL
 BE AS SHOWN IN FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARANCES SHALL BE CLEAR & LEVEL.
  
 7) SHEET A125.4 DOOR # 27 MAY OR MAY NOT MEET THE 18?
 REQUIRED FOR THE LATCH SIDE OF THE DOOR , PLEASE
 PROVIDE MEASUREMENTS. 11-4.13.6 MANEUVERING
 CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARANCES AT DOORS THAT
 ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN FIG. 25. THE FLOOR
 OR GROUND AREA WITH IN THE REQUIRED CLEARANCES SHALL BE
 CLEAR & LEVEL.
  
 8) MISSING SHEET A150.3 REFLECTED CEILING PLAN
 NORTHEAST QUADRANT, 106.1.2 ADDITIONAL INFORMATION
 REQUIRED. TABLE 1006 . > 2 STORIES OR LED OR > 50
 PEOPLE ABOVE OR BELOW.
  
 9) SHEET A400.2 PROVIDE VARIOUS DETAILS OF SOFFITS, THE
 PLANS LACKATTACHMENT OF TOP TRACK TO DECK ABOVE?
  
 10) PLEASE SEE ELECTRICAL NOTE# 1 THAT MAY CREATE A
 PROBLEM BEFORE THE SHELL BUILDING RECEIVES THEIR
 CERTIFICATE OF COMPLETION.)
 BUILDING PLAN REVIEW II
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]