| Date |
Text |
| 2007-08-17 14:39:46 | 1920 WEKIVA WAY 2ND FLOOR BUILD-OUT |
| | |
| | |
| | PERMIT: 07070482 |
| | ADD: 1920 WEKIVA WAY |
| | CONT: ANDERSON-MOORE CONSTRUCTION |
| | ? THE CAPITAL CITY OF THE PALM BEACHES? |
| | TEL: (561)662-1819 |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | 2) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE |
| | WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT |
| | ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| | |
| | 3)PLEASE PROVIDE THE OCCUPANT LOAD THAT WILL BE GOING |
| | THROUGH VARIOUS DOORS. IT APPEARS THAT |
| | SOME OF THE DOORS MAY HAVE AN OCCUPANT LOAD GREATER |
| | THAN 50 REQUIRINGTHE DOOR TO SWING IN THE DIRECTION |
| | OF EGRESS TRAVEL SEE 1008.1.2 AND 1002.1 (DEFINITIONS) |
| | OCCUPANT LOAD. |
| | |
| | 4) SHEET A2.10.1THE BREAK ROOM SINK AND THE |
| | CONFERENCE ROOM SINK WILL BOTH REQUIRE THE FOLLOWING: |
| | SINKS: |
| | 11-4.24.2 SINKS, HEIGHT. SINKS SHALL BE MOUNTED WITH |
| | THE COUNTER NO HIGHER THAN 34" ABOVE THE FINISH FLOOR. |
| | 11-4.24.3 KNEE CLEARANCE THAT IS AT LEAST 27" HIGH 30" |
| | WIDE, AND 19" DEEP SHALL BE PROVIDED UNDERNEATH SINKS. |
| | 11-4.24.5 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE AT |
| | LEAST 30 INCHES BY 48 INCHES (760 MM BY 1219 MM) |
| | COMPLYING WITH SECTION 11-4.2.4 SHALL BE PROVIDED IN |
| | FRONT OF A SINK TO ALLOW FORWARD APPROACH. THE CLEAR |
| | FLOOR SPACE SHALL BE ON AN ACCESSIBLE ROUTE AND SHALL |
| | EXTEND A MAXIMUM OF 19 INCHES (485 MM) UNDERNEATH THE |
| | SINK. |
| | |
| | 5) SHEET A125.2 DOOR # 9 IS MISSING THE 18? ON THE |
| | LATCH SIDE OF THE DOOR. 11-4.13.6 MANEUVERING |
| | CLEARENCES AT DOORS. MINIMUM MANEUVERING CLEARANCES |
| | AT DOORS THAT ARE NOT AUTOMATIC OR POWER-ASSISTED SHALL |
| | BE AS SHOWN IN FIG. 25. THE FLOOR OR GROUND AREA WITH |
| | IN THE REQUIRED CLEARANCES SHALL BE CLEAR & LEVEL. |
| | 6) SHEET A125.3 DOOR# 19 IS ALSO MISSING THE REQUIRED |
| | 18? AT THE LATCH SIDE. 11-4.13.6 MANEUVERING CLEARENCES |
| | AT DOORS. MINIMUM MANEUVERING CLEARANCES |
| | AT DOORS THAT ARE NOT AUTOMATIC OR POWER-ASSISTED SHALL |
| | BE AS SHOWN IN FIG. 25. THE FLOOR OR GROUND AREA WITH |
| | IN THE REQUIRED CLEARANCES SHALL BE CLEAR & LEVEL. |
| | |
| | 7) SHEET A125.4 DOOR # 27 MAY OR MAY NOT MEET THE 18? |
| | REQUIRED FOR THE LATCH SIDE OF THE DOOR , PLEASE |
| | PROVIDE MEASUREMENTS. 11-4.13.6 MANEUVERING |
| | CLEARENCES |
| | AT DOORS. MINIMUM MANEUVERING CLEARANCES AT DOORS THAT |
| | ARE NOT AUTOMATIC OR |
| | POWER-ASSISTED SHALL BE AS SHOWN IN FIG. 25. THE FLOOR |
| | OR GROUND AREA WITH IN THE REQUIRED CLEARANCES SHALL BE |
| | CLEAR & LEVEL. |
| | |
| | 8) MISSING SHEET A150.3 REFLECTED CEILING PLAN |
| | NORTHEAST QUADRANT, 106.1.2 ADDITIONAL INFORMATION |
| | REQUIRED. TABLE 1006 . > 2 STORIES OR LED OR > 50 |
| | PEOPLE ABOVE OR BELOW. |
| | |
| | 9) SHEET A400.2 PROVIDE VARIOUS DETAILS OF SOFFITS, THE |
| | PLANS LACKATTACHMENT OF TOP TRACK TO DECK ABOVE? |
| | |
| | 10) PLEASE SEE ELECTRICAL NOTE# 1 THAT MAY CREATE A |
| | PROBLEM BEFORE THE SHELL BUILDING RECEIVES THEIR |
| | CERTIFICATE OF COMPLETION.) |
| | BUILDING PLAN REVIEW II |
| | JIM WITMER C. B. O. |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | E-MAIL: [email protected] |