| Plan Review Notes For Permit 07070465 |
| Permit Number |
07070465 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-09-26 18:14:36 | 2004 FBC W/2007 REVISIONS | | | INSTALL PANEL WALLS AND SLAB | | | | | | DENIED BY BUILDING | | | | | | 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT | | | MUST BE SUBMITTED BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | 2) THE SIGNED AND SEALED DRAWINGS ARE REQUIRED TO HAVE | | | THE ORIGINAL SIGNATURE OF THE ENGINEER. COPIED | | | SIGNATURES OR SIGNATURE STAMPS ARE NOT ACCEPTABLE. SEE | | | FS 471 AND FAC 61G15-23.002. | | | | | | 3) SUBMIT PRODUCT APPROVALS FOR THE PANEL WALLS, DOORS, | | | ETC. AS REQUIRED BY RULE 9B-72. PROVIDE TEST REPORTS | | | AND INSTALLATION INSTRUCTIONS. | | | SUBMIT THE TEST REPORT AND INSTALLATION INSTRUCTIONS | | | FOR THE SWING DOOR AND THE TEST REPORT FOR THE WALL | | | PANELS. | | | | | | 4)WPB ADMIN CODE 106.3* PRODUCT | | | APPROVALS. THOSE PRODUCT WHICH ARE | | | REGULATED BY DCA RULE 9B-72 SHALL BE | | | REVIEWED AND APPROVED IN WRITING BY THE | | | DESIGNER OF RECORD PRIOR TO SUBMITTAL | | | FOR JURISDICTIONAL APPROVAL. THE ENGINEER IS REQUIRED | | | TO APPROVE THE PRODUCT APPROVALS IN WRITING. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|