| Plan Review Notes For Permit 07070454 |
| Permit Number |
07070454 |
|
| Review Stop |
B |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2007-09-17 16:39:56 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | 1.)THE RESPONSE LETTER STATED THAT I ASKED FOR ANCHOR | | | SPACING BE CHANGED TO 4".THIS WAS NOT WHAT I | | | INTENDED; I STATED THAT 4" WAS REQUIRED FOR SPANS OF | | | 12', WHICH WAS THE SPAN ON THE INSTALLATION SCHEDULE. | | | A NEW INSTALLATION SCHEDULE HAS BEEN PROVIDED AND SPANS | | | ARE FIXED. | | | | | | 2.)SEE SHEET 14 OF THE PRODUCT APPROVAL.AN EDGE | | | DISTANCE OF 3" REQUIRES A FACTOR OF .83 APPLIED TO THE | | | ANCHOR SPACING.PLEASE REVISE. | | | |
|