| 2007-07-19 07:56:22 | |
| | |
| | |
| | NONCOMPLIANT |
| | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE |
| | COMPLIANCE AND RESUBMIT FOR REVIEW. |
| | |
| | 1} PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN, |
| | METER ENCLOSURE, DISCONNECTS AND PANELS, SO THAT |
| | COMPLIANCE WITH ARTICLES 225 AND 230 CAN BE REVIEWED. |
| | |
| | 2} PROVIDE A PANEL SCHEDULE PER 408.4. INCLUDE OCP AND |
| | CONDUCTOR SIZES. |
| | |
| | 3} PROVIDE LOAD CALCULATIONS PER ARTICLE 220 PART III, |
| | STANDARD OR PART IV OPTIONAL, INDICATE METHOD USED. |
| | SMALL APPLIANCE CIRCUITS @ 1500 VA EACH, 2 MINIMUM, |
| | 220.52(A). |
| | |
| | 4} } PER 110.9 AND 110.10: OBTAIN THE |
| | AVAILABLE FAULT CURRENT AT THE UTILITY |
| | AND CALCULATE THE SAME AT THE EQUIPMENT. |
| | INDICATE THE AIC RATING FOR THE |
| | EQUIPMENT IS EQUAL TO OR GREATER THAN |
| | THE AVAILABLE FAULT. |
| | |
| | 5} THE RISER DIAGRAM IS NOT CLEAR. INDICATE IF THERE IS |
| | A METER/ MAIN OR A DISCONNECT DRAWN AS "2P "A". IF A |
| | DISCONNECT IS LOCATED AT THE METER, AN EQUIPMENT GROUND |
| | PER 250.122 MUST BE RAN WITH THE PANEL FEEDER. |
| | |
| | 6} SEE 250.52(A)(3) FOR FOOTER STEEL, INCLUDE AS PART |
| | OF THE REQUIRED GEC SYSTEM WHEN RELOCATING THE SERVICE |
| | AND PUTTING AN ADDITION ON, AS THE FOOTER STEEL IS |
| | "AVAILABLE". |
| | |
| | 7} R313.1.1 SMOKE ALARMS SHALL BE LOCATED AS REQUIRED |
| | IN NEW DWELLINGS WHEN REPAIRS OR ADDITIONS REQUIRING A |
| | PERMIT OCCUR. SEE ARTICLE FOR COMPLETE TEXT. LOCATE ON |
| | PLAN. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561/805-6718 |
| | |