2008-05-21 08:47:27PLUMBING PLAN REVIEW:
 REVISION SHEET P-3 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 1. SHEET P-3 WATER RISER DIAGRAM: BAY 1, AND BAY 2,
 WATER RISER DIAGRAMS HAVE THE WRONG SIZE INDICATED ON
 THEM. SHEET P-1 PLUMBING FLOOR PLAN INDICATES BAY 1,
 POTABLE WATER BEING 1-1/2" AND BAY 2, POTABLE WATER
 BEING CHANGED TO 2", HOWEVER THE WATER RISER DIAGRAMS
 ON SHEET P-3 ARE INDICATING BAY 1, BEING CHANGED TO 2"
 AND BAY 2, AS 1-1/2". PLEASE CORRELATE SHEET P-3 WITH
 SHEET P-1 AND CORRECTLY CHANGE THE SIZE OF BAY 1, WATER
 RISER DIAGRAM TO 1-1/2" AND BAY 2, TO 2". PER (W.P.B.
 AS AMENDED) SECTION 106.1.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS AND FBC-2004 PLUMBING SECTION 601.1 SCOPE.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  