Plan Review Notes
Plan Review Notes For Permit 07070444
Permit Number 07070444
Review Stop E
Sequence Number 4
Notes
Date Text
2008-05-27 12:58:57** DENIED REVIEW/REVISION**
  
 ** PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING. PLEASE ALSO SEE SOME NEW NOTES
 AS PLANS/ITEMS HAVE BEEN REVISED FROM PREVIOUS PLANS
 REVIEWED.
  
  
 1) NOTE: PLEASE SEE THAT PLANS NEED TO BE COMPLETE FOR
 LIGHTING INCLUDING THE FIXTURE LEGEND IN ORDER TO FIND
 COMPLIANCE WITH THE ENERGY CODE COMPLIANCE. THE INPUT
 DATA REPORT CAN NOT BE VERIFIED AT THIS TIME FOR ALL
 ITEMS AS THE FIXTURE LEGEND ON PLANS IS NOT COMPLETE.
 PLEASE SEE THAT ALL LIGHTING ON PLANS NEEDS TO
 CORRELATE WITH THE IDR SUBMITTED. PLEASE SEE ONE
 EXAMPLE WOULD BE EXTERIOR LIGHTING. PLEASE SEE BASED ON
 THE NUMBER OF FIXTURES, THE WATTAGE OF FIXTURES ON
 PLANS THE IDR DOES NOT CORRELATE.
 PLEASE LOOK AT THE FIXTURES, COMPLETE THE WATTAGES AND
 COORDINATE ALL.
 13-415.2.ABC.1.1, .1.2 AND .1.3.
 PLEASE SEE EXTERIOR FIXTURES SEEM TO BE THE MOST
 PREVALENT LOCATION FOR NEED OF COORDINATION.
 ** PLEASE SEE COMMENT #2 BELOW.
  
 ** PLEASE BE SURE THE OWNER AGENT IS FILLED OUT ON THE
 CERTIFICATION SHEET.
  
 2) NOTE: PLEASE SEE THE WATTAGES SHOWN ON THE
 CALCULATIONS/PANEL SCHEDULES ALSO DO NOT COORDINATE
 WITH THE IDR. PLEASE SEE CIRCUIT H-6 FOR EXAMPLE. IF
 ACTUALLY USING THE WATTAGE SHOWN ON THE LEGEND OR THE
 IDR OF ENERGY CALCULATIONS HOW IS IT THE WATTAGE SHOWN
 ON PANEL SCHEDULE IS THAT MUCH LOWER?
 PLEASE COORDINATE. 220.12, 220.42,FBC CHAPTER
 13,13-415.2.ABC.1.3
  
 3) NOTE: PLEASE KNOW THE ARCHITECTURAL TITLE BLOCK IS
 NOT REQUIRED TO BE PLACED ON ELECTRICAL SHEETS.
 APPLICATION FOR CERTIFICATE OF AUTHORIZATION NUMBER
 LICENSE THROUGH THE STATE IS STILL IN PROGRESS. PLEASE
 SEE ATTACHED PRINT OUT FROM DBPR.
 FS 481.219
  
 4) NOTE: PLEASE SEE THE RISER ON EG-1 IS STILL SHOWING
 *EQUIPMENT GROUNDING CONDUCTORS* BEFORE THE FIRST MEANS
 OF DISCONNECT WHICH IS NOT PERMITTED PER 250.6.
 THESE WERE REMOVED FROM E-2
  
 5) NOTE: PLEASE SEE THE GROUNDING ELECTRODE DETAIL ON
 PREVIOUS PLANS AS WELL AS EG-1 WHICH USED TO INCLUDE
 THE FOOTER STEEL HOWEVER THE REVISED E-2 NOW SHOWS NO
 FOOTER STEEL WHEN IN FACT THIS WAS PART OF THE
 FOUNDATION PERMIT AND IS A REQUIRED ATTACHMENT PER
 250.50. PLEASE BE SURE TO PLACE THIS BACK ON PLANS AS
 SHOWN ON EG-1.
  
 6) NOTE: PLEASE KNOW AS ONLY ONE SERVICE RISER IS NOW
 BEING SHOWN FOR REVIEW PLEASE BE SURE TO LABEL ALL
 MAINS PER 230.2E. FOR EXAMPLE:
 MAIN 1 OF 4, 2 OF 4, ETC
  
 7) NOTE: PLEASE KNOW ALL LIGHTING ON PLANS IN SPACES
 PARTICULARLYTHE BAY #2 WILL BE REQUIRED TO BE REVISED
 IF THE BUILD OUT SPACES IS PERMITTED BEFORE CERTIFICATE
 OF COMPLETION IS ISSUED FOR SHELL BUILDING.
 PLEASE KNOW THESE ARE THE LIGHTS SHOWN ON HOUSE PANEL
 CIRCUITS SUCH AS EXIT, EMERGENCY LIGHTS. THESE SHALL
 REMAIN UNTIL BUILD OUT PERMIT IS ISSUED.
 ONLY NOTED FOR COORDINATION.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF
 THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT
 HESITATE IN CONTACTING THIS OFFICE.
  
 ** IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]