| Date |
Text |
| 2008-03-20 13:03:54 | ** DENIEDREVIEW ** |
| | |
| | |
| | ** PLEASE SEE SOME COMMENTS BELOW ARE STILL THE SAME AS |
| | THE COMMENTS GENERATE ON SERVICE UNDER THE STAPLES |
| | BUILD OUT REVIEW. |
| | |
| | |
| | 1) NOTE: PLEASE SEE THE CODES TO BE LISTED ON PLANS ARE |
| | REQUIRED TO BE LISTED AS OF THE LATEST ADOPTED CODES |
| | WHEN PERMIT APPLICATION IS MADE. |
| | PLEASE SEE THERE ARE CODES LISTED ON ELECTRICAL PLANS |
| | WHICH ARE NO LONGER IN AFFECT, HAVE BEEN UPDATED OR DO |
| | NOT SHOW ANY DATES |
| | 2004 FBC W/ 2007 REVISIONS SHOWS ON PLANS 2004 FBC WITH |
| | 2005 REVISIONS. |
| | 2005 NFPA-70, SHOWS 2002 NFPA-70 |
| | 2003 NFPA-101, DOES NOT SHOW ANY SPECIFIC ADOPTED |
| | CODE. |
| | |
| | PLEASE BE SURE TO SEE ANY CODES WHICH OTHER TRADE |
| | REVIEWERS MAY REQUEST. |
| | |
| | 2) NOTE: PLEASE SEE ELECTRICAL RISER/ SERVICE SHEET IS |
| | STILL SHOWING TWO COMPLETELY DIFFERENT SERVICES TO BE |
| | INSTALLED. |
| | RISER DOES NOT ANY MSB, YET THE SHEET E-2 STILL SHOWS A |
| | MSB WHICH NOTES FEEDING EACH BAY. |
| | HOW IS THIS POSSIBLE WHEN THE RISER SHOWS SEPARATE |
| | METERS AND MAINS FOR EACH TENANT TO GUTTER? |
| | PLEASE SEE THE SERVICE CONDUCTORS COMING IN FOR EACH DO |
| | NOT CORRELATE. |
| | PLEASE SEE THAT CONDUCTORS SHALL BE BASED ON SERVICE. |
| | PLEASE COORDINATE ALL AND ONCE ONE SERVICE IS DONE A |
| | FULL AND COMPLETE REVIEW CAN BE DONE. PLEASE SEE SOME |
| | OTHER COMMENTS BELOW WITH RESPECT TO THE SERVICE RISER |
| | WHICH IS NOT CODE COMPLIANT. |
| | 240.4, 310.16, 230.70, 230.71, ETC. |
| | FBC 106.1.2, 106.3.5.1.2 FOR COORDINATION AND |
| | CORRELATION. |
| | |
| | 3) NOTE: PLEASE SEE THE CONDUCTORS TO PANEL *L* ON |
| | RISER DO NOT CORRELATE WITH THE CONDUCTORS ON THE RISER |
| | TO THIS SAME PANEL FROM THE TRANSFORMER. |
| | 310.16, 240.4, |
| | FBC 106.1.2 FOR COORDINATION. |
| | |
| | 4) NOTE: PLEASE SEE 250.6, 250.24 AS *EQUIPMENT |
| | GROUNDING CONDUCTORS* MAY ONLY BE INSTALLED *AFTER* THE |
| | FIRST MEANS OF DISCONNECT. |
| | PLEASE SEE RISER WHICH SHOWS EQUIPMENT GROUNDING |
| | CONDUCTORS BEFORE MAINS? |
| | |
| | 5) NOTE: PLEASE SEE 13-415.1.ABC.1.1, .1.2, .1.3 AND |
| | .1.4. |
| | PLEASE SEE THAT ALL LIGHTING IN INTERIOR SHALL BE |
| | REQUIRED TO CONTAIN AUTOMATED CONTROLS. ONE EXAMPLE |
| | WHICH DOES NOT SHOW ENOUGH INFORMATION IS BAY #3 WHICH |
| | SHOWS ONLY A STANDARD SWITCH. |
| | PLEASE KNOW, LIGHTING IN BAY #2 MAY BE REQUIRED IF THE |
| | PERMIT APPLICATION FOR THE BUILD OUT OF STAPLES IS NOT |
| | COMPLETED AND ISSUED BEFORE CO OF SPACE. |
| | PLEASE SEE NO INFORMATION FOR CONTROL OF EXTERIOR |
| | LIGHTING CONTROLS WAS SUBMITTED OR SHOWN AS REQUIRED BY |
| | SECTION .1.4 NOTED ABOVE. |
| | |
| | 6) NOTE: PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED |
| | DO NOT CORRELATE WITH PLANS. |
| | PLEASE SEE THE SQ FT DOES NOT MATCH WITH ARCHITECTURAL |
| | PLANS. |
| | PLEASE SEE THE ADDRESS STILL SHOWS 2015 WHICH WAS NOTED |
| | ON MULTIPLE REVIEWS PREVIOUSLY. THIS ADDRESS IS 2029. |
| | PLEASE ADJUST. |
| | PLEASE SEE THE LIGHTING PLACED INTO THE INPUT DATA |
| | REPORT FOR EXTERIOR LIGHTING DOES NOT MATCH WITH PLANS. |
| | PLEASE SEE THERE ARE MULTIPLE TYPES OF FIXTURES ON |
| | PLANS WHEN THE IDR ONLY SHOWS TWO TYPES OF FIXTURES. |
| | ALSO IN EITHER CASE THE NUMBER OF FIXTURES AND THE |
| | WATTAGE OF EACH DO NOT CORRELATE WITH PLANS. |
| | 13-415.2.ABC .1.3 FOR EXTERIOR LIGHTING. |
| | PLEASE SEE 13-400.3.B OR 13-400.3.C, 13-101.1.6 FOR |
| | SHELL BUILDINGS AND REQUIRED LIGHTING. |
| | PLEASE CLARIFY LIGHTING WHICH WILL BE IN PARKING LOTS. |
| | |
| | FOR EXAMPLE: FRONT LOT ONLY SHOWS THREE POLE LIGHTS?? |
| | THERE IS MORE THAN THIS LOCATED ON SITE. |
| | |
| | 7) NOTE: PLEASE BAY AREA WILL REQUIRED SOME SORT OF |
| | EGRESS LIGHTING FOR NORMAL AND EMERGENCY CONDITIONS. |
| | THE BAY NOW SHOWS OCCUPANCY SENSORS, HOWEVER NO |
| | LIGHTING? SPACE IN FACT SHOWS 21 OS TYPE DEVICES |
| | HOWEVER NO CONNECTION DETAILS ETC. |
| | 13-415.1.ABC.1.1, LS 101 7.8, 7.9, NEC 700.12F, 700.16 |
| | ETC |
| | FBC 106.1.2, 106.3.5.1.2 FOR ADDITIONAL INFORMATION. |
| | |
| | 8) NOTE: PLEASE SEE THE ELECTRICAL PERMIT APPLIED FOR |
| | #08020101 HAD A BALANCE OWED FOR THE APPLIED VALUE. THE |
| | VALUE NEEDS TO NOW BE INCREASED ON SHELL PERMIT. THIS |
| | PERMIT WAS ORIGINALLY FOR SOME STRUCTURAL ONLY WHICH |
| | APPLIED VALUE WAS $170K. THE SCOPE OF WORK SINCE |
| | ORIGINAL APPLICATION HAS SUBSTANTIALLY INCREASED YET |
| | THE APPLIED VALUE WAS NOT INCREASED BY CONTRACTOR. |
| | PLEASE INCREASE VALUE FOR COMPLETE SHELL BUILDING. |
| | FBC 108.3 |
| | |
| | |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |