2008-03-20 13:03:54** DENIEDREVIEW **
  
  
 ** PLEASE SEE SOME COMMENTS BELOW ARE STILL THE SAME AS
 THE COMMENTS GENERATE ON SERVICE UNDER THE STAPLES
 BUILD OUT REVIEW.
  
  
 1) NOTE: PLEASE SEE THE CODES TO BE LISTED ON PLANS ARE
 REQUIRED TO BE LISTED AS OF THE LATEST ADOPTED CODES
 WHEN PERMIT APPLICATION IS MADE.
 PLEASE SEE THERE ARE CODES LISTED ON ELECTRICAL PLANS
 WHICH ARE NO LONGER IN AFFECT, HAVE BEEN UPDATED OR DO
 NOT SHOW ANY DATES
 2004 FBC W/ 2007 REVISIONS SHOWS ON PLANS 2004 FBC WITH
 2005 REVISIONS.
 2005 NFPA-70, SHOWS 2002 NFPA-70
 2003 NFPA-101, DOES NOT SHOW ANY SPECIFIC ADOPTED
 CODE.
  
 PLEASE BE SURE TO SEE ANY CODES WHICH OTHER TRADE
 REVIEWERS MAY REQUEST.
  
 2) NOTE: PLEASE SEE ELECTRICAL RISER/ SERVICE SHEET IS
 STILL SHOWING TWO COMPLETELY DIFFERENT SERVICES TO BE
 INSTALLED.
 RISER DOES NOT ANY MSB, YET THE SHEET E-2 STILL SHOWS A
 MSB WHICH NOTES FEEDING EACH BAY.
 HOW IS THIS POSSIBLE WHEN THE RISER SHOWS SEPARATE
 METERS AND MAINS FOR EACH TENANT TO GUTTER?
 PLEASE SEE THE SERVICE CONDUCTORS COMING IN FOR EACH DO
 NOT CORRELATE.
 PLEASE SEE THAT CONDUCTORS SHALL BE BASED ON SERVICE.
 PLEASE COORDINATE ALL AND ONCE ONE SERVICE IS DONE A
 FULL AND COMPLETE REVIEW CAN BE DONE. PLEASE SEE SOME
 OTHER COMMENTS BELOW WITH RESPECT TO THE SERVICE RISER
 WHICH IS NOT CODE COMPLIANT.
 240.4, 310.16, 230.70, 230.71, ETC.
 FBC 106.1.2, 106.3.5.1.2 FOR COORDINATION AND
 CORRELATION.
  
 3) NOTE: PLEASE SEE THE CONDUCTORS TO PANEL *L* ON
 RISER DO NOT CORRELATE WITH THE CONDUCTORS ON THE RISER
 TO THIS SAME PANEL FROM THE TRANSFORMER.
 310.16, 240.4,
 FBC 106.1.2 FOR COORDINATION.
  
 4) NOTE: PLEASE SEE 250.6, 250.24 AS *EQUIPMENT
 GROUNDING CONDUCTORS* MAY ONLY BE INSTALLED *AFTER* THE
 FIRST MEANS OF DISCONNECT.
 PLEASE SEE RISER WHICH SHOWS EQUIPMENT GROUNDING
 CONDUCTORS BEFORE MAINS?
  
 5) NOTE: PLEASE SEE 13-415.1.ABC.1.1, .1.2, .1.3 AND
 .1.4.
 PLEASE SEE THAT ALL LIGHTING IN INTERIOR SHALL BE
 REQUIRED TO CONTAIN AUTOMATED CONTROLS. ONE EXAMPLE
 WHICH DOES NOT SHOW ENOUGH INFORMATION IS BAY #3 WHICH
 SHOWS ONLY A STANDARD SWITCH.
 PLEASE KNOW, LIGHTING IN BAY #2 MAY BE REQUIRED IF THE
 PERMIT APPLICATION FOR THE BUILD OUT OF STAPLES IS NOT
 COMPLETED AND ISSUED BEFORE CO OF SPACE.
 PLEASE SEE NO INFORMATION FOR CONTROL OF EXTERIOR
 LIGHTING CONTROLS WAS SUBMITTED OR SHOWN AS REQUIRED BY
 SECTION .1.4 NOTED ABOVE.
  
 6) NOTE: PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED
 DO NOT CORRELATE WITH PLANS.
 PLEASE SEE THE SQ FT DOES NOT MATCH WITH ARCHITECTURAL
 PLANS.
 PLEASE SEE THE ADDRESS STILL SHOWS 2015 WHICH WAS NOTED
 ON MULTIPLE REVIEWS PREVIOUSLY. THIS ADDRESS IS 2029.
 PLEASE ADJUST.
 PLEASE SEE THE LIGHTING PLACED INTO THE INPUT DATA
 REPORT FOR EXTERIOR LIGHTING DOES NOT MATCH WITH PLANS.
 PLEASE SEE THERE ARE MULTIPLE TYPES OF FIXTURES ON
 PLANS WHEN THE IDR ONLY SHOWS TWO TYPES OF FIXTURES.
 ALSO IN EITHER CASE THE NUMBER OF FIXTURES AND THE
 WATTAGE OF EACH DO NOT CORRELATE WITH PLANS.
 13-415.2.ABC .1.3 FOR EXTERIOR LIGHTING.
 PLEASE SEE 13-400.3.B OR 13-400.3.C, 13-101.1.6 FOR
 SHELL BUILDINGS AND REQUIRED LIGHTING.
 PLEASE CLARIFY LIGHTING WHICH WILL BE IN PARKING LOTS.
  
 FOR EXAMPLE: FRONT LOT ONLY SHOWS THREE POLE LIGHTS??
 THERE IS MORE THAN THIS LOCATED ON SITE.
  
 7) NOTE: PLEASE BAY AREA WILL REQUIRED SOME SORT OF
 EGRESS LIGHTING FOR NORMAL AND EMERGENCY CONDITIONS.
 THE BAY NOW SHOWS OCCUPANCY SENSORS, HOWEVER NO
 LIGHTING? SPACE IN FACT SHOWS 21 OS TYPE DEVICES
 HOWEVER NO CONNECTION DETAILS ETC.
 13-415.1.ABC.1.1, LS 101 7.8, 7.9, NEC 700.12F, 700.16
 ETC
 FBC 106.1.2, 106.3.5.1.2 FOR ADDITIONAL INFORMATION.
  
 8) NOTE: PLEASE SEE THE ELECTRICAL PERMIT APPLIED FOR
 #08020101 HAD A BALANCE OWED FOR THE APPLIED VALUE. THE
 VALUE NEEDS TO NOW BE INCREASED ON SHELL PERMIT. THIS
 PERMIT WAS ORIGINALLY FOR SOME STRUCTURAL ONLY WHICH
 APPLIED VALUE WAS $170K. THE SCOPE OF WORK SINCE
 ORIGINAL APPLICATION HAS SUBSTANTIALLY INCREASED YET
 THE APPLIED VALUE WAS NOT INCREASED BY CONTRACTOR.
 PLEASE INCREASE VALUE FOR COMPLETE SHELL BUILDING.
 FBC 108.3
  
  
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved