2008-05-22 14:08:40REVIEW #: 2ND
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1 THROUGH 3: OK
  
 4. AS STATED IN PREVIOUS REVIEW COMMENT, THIS AREA IS
 DESIGNED AS AN EXIT PASSAGEWAY AS SHOWN ON PAGE A2.1.
 PENETRATIONS INTO AND OPENINGS THROUGH AN EXIT
 PASSAGEWAY ARE PROHIBITED EXCEPT FOR REQUIRED EXIT
 DOORS, EQUIPMENT AND DUCTWORK NECESSARY FOR INDEPENDENT
 PRESSURIZATION IN ACCORDANCE WITH FBCB 1020.5. THE DUCT
 PENETRATION, EVEN WITH A FIRE DAMPER IS PROHIBITED PER
 THIS SECTION. THIS IS A PASSIVE AIR TRANSFER DUCT AND
 DOES NOT SERVE AS PART OF A REQUIRED EXIT ENCLOSURE
 PRESSURIZATION SYSTEM. NO PRESSURIZATION OF THIS EXIT
 PASSAGEWAY IS REQUIRED. REMOVE ANY PENETRATIONS INTO
 THIS EXIT PASSAGEWAY WHICH ARE NOT SPECIFICALLY ALLOWED
 UNDER FBCB 1020.5. THE OPENING WITH LOUVER DIRECTLY TO
 THE OUTDOORS FROM THE EXIT PASSAGEWAY IS NOT
 PROHIBITED.
 NOTE: THIS IS NOT A DETRMINATION BASED ON PLAN REVIEW
 THAT AN EXIT PASSAGEWAY IS REQUIRED AT THIS LOCATION.
 THE REQUIREMENT FOR COMPLIANCE WITH FBCB 1020.5 IS
 BASED ON THE DESIGN INTENT AS SHOWN ON PAGES A2.1 AND
 A8.2.
  
 5. OK. BUTLER SHOP DRAWINGS AND ROOF CURB REQUIREMENTS
 TO BE VERIFIED BY BUILDING PLAN REVIEWER.